Description
1. Basic Information
表格
| Item | Content |
|---|---|
| Model | 1SVR011718R2500 (Type: CC‑E I/I) |
| Manufacturer | ABB |
| Series | CC‑E Signal Converter Series |
| Product Type | Single‑function 4‑20 mA Isolated Current Signal Converter |
| Mounting | DIN‑rail mounting (EN 60715) |
| Supply Voltage | 24 VDC (18‑30 VDC) |
| Power Consumption | Approx. 2 W |
| Status Indicator | Green LED for power supply status |
| Warranty | 12‑month factory warranty |
| BOM Full‑Name | 1SVR011718R2500, CC‑E I/I Analogue Signal Converter, 4‑20mA Input / 4‑20mA Output, 3‑Way Isolation |
| BOM Short‑Name | 1SVR011718R2500‑Signal Converter, CC‑E I/I, 1‑Ch 4‑20 mA Isolator |
2. Electrical Specifications
- Channel count: 1 input channel, 1 output channel
- Fixed input signal: 4‑20 mA
- Fixed output signal: 4‑20 mA
- Isolation: 3‑way galvanic isolation (Input / Output / Power supply)
- Isolation test voltage: 2.5 kV AC, 1 minute
- Basic accuracy: ±0.2 % of full scale
- Adjustment: Gain and offset trimming via front‑panel potentiometers
- Output load: ≤ 500 Ω for 4‑20 mA current output
- Input impedance: ≤ 50 Ω
- Response time: ≤ 1 ms
- Protection: Short‑circuit proof output, reverse‑polarity protection for power supply
3. Environmental Conditions
- Operating temperature: ‑20 ℃ ~ +70 ℃
- Storage temperature: ‑40 ℃ ~ +85 ℃
- Relative humidity: 5‑95 % RH, non‑condensing
- Approvals & standards: CE, UL508, RoHS, EN 50178, IEC 61000‑6‑2
- Enclosure rating: IP20 (module surface)
- Dimensions (W×H×D): 22.5 mm × 107 mm × 75 mm
- Weight: 85 g
4. Main Functions
- Galvanic isolation for 4‑20 mA current loops, breaks ground loops between field transmitters and DCS / PLC analogue input modules.
- Fixed 4‑20 mA input to 4‑20 mA output conversion; fine calibration of gain and offset by front potentiometers.
- Three‑way isolation protects control‑system side from field‑side interference and surge transients.
- Compact DIN‑rail installation inside control cabinets for process‑automation signal conditioning.
- Product lifecycle status: End‑of‑Life, no new production by ABB; procure spare‑parts with full part‑number.
5. Typical Applications
- Process industry: 4‑20 mA signal isolation between field transmitters and DCS / PLC analogue inputs.
- Power plant, water‑waste‑water, petrochemical control panels for ground‑loop elimination in analogue measurement loops.
Related CC‑E series reference|Part‑No|Description|Remark|
|—|—|—|
|1SVR011718R2500|CC‑E I/I 4‑20mA /4‑20mA Signal Converter|Discontinued|
|1SVR011700R0000|CC‑E/STD Universal Analogue Signal Converter|Discontinued|
6. Important Notes
- This is fixed‑range I‑I converter, not universal configurable type; input and output are locked to 4‑20 mA.
- Observe maximum output load resistance ≤ 500 Ω, excessive load will degrade signal accuracy.
- Gain‑offset trimming should be performed during commissioning for site calibration.
- Full ordering part‑number 1SVR011718R2500 must be used for spare‑part purchasing.






-300x300.jpg)
Reviews
There are no reviews yet.