Description
1. Basic Information
表格
| Item | Content |
|---|---|
| Model | 1TGE120021R0010 (Type: MLink) |
| Manufacturer | ABB |
| Series | MNS‑iS Intelligent MCC System |
| Product Type | Embedded Communication Gateway Module |
| Mounting | Rack‑mount inside MNS‑iS MCC cubicle |
| Supply Voltage | 24 VDC (18‑30 VDC) |
| Power Consumption | Approx. 25 W |
| Status Indicator | Multi‑colour LED indicators for Power, CPU, LAN, Service status |
| Configuration Tool | MNavigate configuration software |
| Warranty | 12‑month factory warranty |
| BOM Full‑Name | 1TGE120021R0010, MLink Communication Gateway Module for MNS‑iS MCC System |
| BOM Short‑Name | 1TGE120021R0010‑MLink, MNS‑iS Communication Gateway |
2. Electrical & Interface Specifications
- On‑board Interfaces: 2 × Ethernet ports, RS‑485 field bus interface, RS‑232 service port, local HMI interface
- Internal bus: MNS‑iS back‑plane bus for communication with MControl motor‑control units
- Supported protocols: Modbus TCP, Modbus RTU, proprietary MNS‑iS internal protocol
- Function: Data collection of motor status, fault alarms, current/voltage measurement values; forward commands from upper system to motor‑control units
- Isolation: Galvanic isolation between field bus and Ethernet interfaces
- No direct process I/O channels; purely communication gateway hardware
3. Environmental Conditions
- Operating temperature: 0 ℃ ~ +55 ℃ (inside MCC cubicle)
- Storage temperature: ‑40 ℃ ~ +85 ℃
- Relative humidity: 5‑95 % RH, non‑condensing
- Approvals & standards: CE, IEC 61850‑3, IEC 61000‑6‑2
- Enclosure rating: IP20
- Dimensions (W×H×D): 280 mm × 130 mm × 210 mm
- Weight: 2.1 kg
4. Main Functions
- Central communication gateway for MNS‑iS intelligent MCC, collects real‑time status, measurement data and fault events from multiple MControl motor‑protection units.
- Protocol conversion between internal MNS‑iS bus and standard Modbus TCP / RTU for connection to DCS, SCADA and plant monitoring systems.
- Route remote control commands (motor start / stop, reset) from upper‑level system down to individual motor‑control units.
- Local service access via service port for parameter setting, diagnostic readout and firmware upgrade using MNavigate software.
- Provide system‑wide time‑synchronisation for connected MNS‑iS devices.
- Product lifecycle status: End‑of‑Life, ABB no longer manufactures new units; procure spare parts with complete part‑number only.
5. Typical Applications
- Large‑scale industrial low‑voltage motor control centres (MNS‑iS MCC cabinets) for petrochemical, power‑plant auxiliary systems, water‑treatment plants.
- Real‑time monitoring and remote control of dozens to hundreds of LV motors integrated with plant‑wide DCS/SCADA.
Related MNS‑iS reference|Part‑No|Description|Remark|
|—|—|—|
|1TGE120021R0010|MLink Communication Gateway|MNS‑iS central gateway, discontinued|
|MControl series|Motor control & protection units|Field devices under MLink management|
6. Important Notes
- This gateway is dedicated exclusively for MNS‑iS MCC system; cannot be used as general‑purpose standalone Modbus gateway for third‑party devices.
- Configuration must be performed with ABB proprietary MNavigate software; no manual DIP‑switch setup.
- Observe 24 VDC power‑supply range; voltage over‑range will damage module hardware.
- Full ordering part‑number 1TGE120021R0010 must be used for spare‑part purchasing.