ABB 1TGE120021R0110 MLink Communication Gateway Module with PROFIBUS‑DP for MNS‑iS Intelligent MCC System

1TGE120021R0110 (MLink) is embedded communication gateway module for ABB MNS‑iS intelligent low‑voltage MCC system, equipped with PROFIBUS‑DP slave interface. It collects motor‑unit data, executes protocol conversion and enables remote motor control between MControl field units and upper‑level DCS/PLC via PROFIBUS‑DP. This model is end‑of‑life by manufacturer.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

1. Basic Information

表格
Item Content
Model 1TGE120021R0110 (Type: MLink, HW V2, PROFIBUS‑DP)
Manufacturer ABB
Series MNS‑iS Intelligent MCC System
Product Type Embedded Communication Gateway Module with PROFIBUS‑DP Interface
Mounting Rack‑mount installation inside MNS‑iS MCC cubicle
Supply Voltage 24 VDC (18‑30 VDC)
Power Consumption Approx. 25 W
Status Indicator Multi‑colour LED indicators for Power, CPU, LAN, PROFIBUS, Service status
Configuration Tool MNavigate configuration software, CF‑card parameter download
Warranty 12‑month factory warranty
BOM Full‑Name 1TGE120021R0110, MLink Communication Gateway Module with PROFIBUS‑DP for MNS‑iS MCC System
BOM Short‑Name 1TGE120021R0110‑MLink, MNS‑iS Gateway, PROFIBUS‑DP Version

2. Electrical & Interface Specifications

  • On‑board Interfaces: 2 × Ethernet ports, PROFIBUS‑DP slave interface, RS‑485 internal MNS‑iS bus, RS‑232 service port, local HMI interface
  • Internal bus: MNS‑iS back‑plane bus for data exchange with MControl motor‑control units
  • Supported protocols: PROFIBUS‑DP (DP‑V0 / DP‑V1), Modbus TCP, proprietary MNS‑iS internal protocol
  • Function: Collect motor measurement values, status and fault events; forward start/stop/reset commands from upper‑level controller to MControl units
  • Isolation: Galvanic isolation between PROFIBUS‑DP, Ethernet and internal MCC bus
  • No physical process I/O channels; pure communication gateway
  • Time synchronisation: Built‑in NTP server function for MNS‑iS device time synceero

3. Environmental Conditions

  • Operating temperature: 0 ℃ ~ +55 ℃ (inside MCC cubicle)
  • Storage temperature: ‑40 ℃ ~ +85 ℃
  • Relative humidity: 5‑95 % RH, non‑condensing
  • Approvals & standards: CE, IEC 61850‑3, IEC 61000‑6‑2
  • Enclosure rating: IP20
  • Dimensions (W×H×D): 280 mm × 130 mm × 210 mm
  • Weight: 2.1 kg

4. Main Functions

  1. Central communication gateway for MNS‑iS intelligent MCC system, acquiring real‑time motor status, measurement data and fault alarms from multiple MControl motor‑protection units.
  2. Protocol conversion between internal MNS‑iS bus and PROFIBUS‑DP for connection to DCS / PLC master controllers.
  3. Transmit remote control commands (motor start, stop, fault reset) from upper‑level system down to individual motor‑control units.
  4. Local commissioning via RS‑232 service port for parameter download, diagnostics and firmware upgrade by MNavigate software. Configuration parameters can be pre‑loaded via CF‑card before power‑oneero.
  5. Provides NTP time‑synchronisation service for all connected MNS‑iS field devices.
  6. Product lifecycle status: End‑of‑Life, ABB stops new production; only spare‑part or surplus stock available.

5. Typical Applications

  1. Petrochemical, power‑plant auxiliary, water‑treatment large‑scale low‑voltage intelligent MCC cabinets (MNS‑iS).
  2. Remote monitoring and control of large quantity LV motors via PROFIBUS‑DP connected to plant DCS / PLC systems.
Related MLink variant reference

|Part‑No|Description|Remark|

|—|—|—|

|1TGE120021R0010|MLink Gateway, Modbus TCP/RTU version|No PROFIBUS‑DP port, discontinued|

|1TGE120021R0110|MLink Gateway, PROFIBUS‑DP slave version|With PROFIBUS‑DP interface, discontinued|

6. Important Notes

  1. This gateway is dedicated for MNS‑iS MCC system only; cannot serve as general‑purpose PROFIBUS gateway for third‑party devices.
  2. Configuration must use ABB proprietary MNavigate software; no hardware DIP‑switch setup. Parameter download via CF‑card is supported for cold commissioning.
  3. PROFIBUS‑DP operates as slave mode only, cannot act as PROFIBUS master.
  4. Strictly observe 24 VDC auxiliary power‑supply range to avoid hardware damage.
  5. Full ordering part‑number 1TGE120021R0110 must be used for spare‑part procurement.