ABB AX670 3BSE000566R1 Table Description:AX670, Mixed Analog I/O Module, 3BSE000566R1

AX670 (3BSE000566R1) is ABB Advant500 / MOD300 DCS mixed analog input‑output eurocard module. It provides 8 analog input channels and 8 analog output channels for 4‑20 mA and 0‑10 V DC signals, equipped with group‑wise galvanic isolation and built‑in channel‑level diagnosis. This component is fully obsolete and only available for legacy DCS equipment maintenance.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

General Information

表格
Item Specification
Part Number AX670, 3BSE000566R1
Manufacturer ABB
Product Family Advant 500 / MOD300 DCS System
Product Type Analog Mixed Input‑Output Module
Installation Advant 500 I/O rack, eurocard plug‑in format
Power Supply 5 VDC / 24 VDC rack backplane power supply
Lifecycle Status Obsolete / End‑of‑Life. OEM manufacturing discontinued. Only new‑old‑stock, refurbished and field‑pulled used maintenance spare parts available; no brand‑new factory‑built units can be ordered.
ESD Handling Requirement Mixed‑signal analog PCB with high‑precision ADC/DAC chips. Anti‑static wrist‑strap and anti‑static workstation must be used during installation, replacement and inspection operations.

Electrical & Interface Specifications

  • Backplane Interface: Gold‑plated eurocard edge connector, connects to Advant 500 rack system bus for power supply, data bus and control signals.
  • Field Signal Interface: External field wiring via dedicated termination unit.
  • Channel Configuration: Mixed analog I/O; 8 analog input channels + 8 analog output channels.
  • Signal Ranges

    Analog Input: 0‑20 mA, 4‑20 mA, 0‑10 V DC

    Analog Output: 0‑20 mA, 4‑20 mA, 0‑10 V DC

  • Resolution: 12‑bit for both ADC and DAC
  • Accuracy: Max ±0.1 % of full scale
  • Output Load Requirement: Current output max 600 Ω; voltage output min 2 kΩ
  • Protection: Channel short‑circuit protection, over‑voltage input clamping protection.
  • On‑Board Circuitry: Analog signal conditioning circuits, multi‑channel ADC, DAC output drivers, galvanic group‑wise isolation, hardware self‑diagnosis logic.
  • Power Consumption: Typical 8‑10 W under full‑load operating condition.
  • Operation Limitation: Cannot operate standalone. Must be deployed within complete Advant 500 / MOD300 rack system, cooperating with controller, backplane and matching termination hardware.
  • Compatibility Matrix
    • Compatible System: ABB Advant 500, MOD300 legacy DCS
    • Mounting: Dedicated eurocard slot in Advant I/O rack
    • Hot‑swap: Not supported; power‑down required for module replacement.

Environmental Specifications

表格
Item Value
Operating Temperature 0 °C ~ +55 °C inside ventilated control cabinet
Storage Temperature ‑40 °C ~ +85 °C for long‑term spare‑part preservation
Relative Humidity 5 %‑95 % RH, non‑condensing; condensation will cause connector corrosion and signal drift risk.
Compliance Standard CE conformity for industrial automation environment
Protection Class IP00 bare printed‑circuit assembly; must be fully enclosed inside DCS cabinet housing.
Physical Dimension Standard eurocard plug‑in form‑factor
Net Weight Approx. 0.42 kg
Conformal Coating: Factory‑applied conformal coating option for harsh industrial site conditions.
Vibration Resistance Complies with IEC 60068‑2‑6 industrial cabinet vibration criteria; severe mechanical shock shall be avoided during transportation and installation.

Main Functions

  1. AX670 (3BSE000566R1) is mixed analog input‑output eurocard module for legacy ABB Advant 500 / MOD300 DCS system. It realizes both field analog signal acquisition and analog control output in one single board.
  2. 8‑channel analog input collects 4‑20 mA / 0‑10 V process signals from transmitters, sensors for pressure, flow, level and temperature measurement.
  3. 8‑channel analog output converts controller set‑point values into 4‑20 mA /0‑10 V analog signals to drive field control devices such as control valves and positioners.
  4. Group‑wise galvanic isolation separates field‑side signals from internal DCS bus circuits, suppressing industrial electromagnetic interference and surge damage.
  5. Module hardware self‑diagnosis monitors channel status, detects open‑loop, short‑circuit and module internal faults, and reports fault codes to Advant operator station for maintenance guidance.
  6. Typical field failure symptoms
    • Partial or full channel signal loss for AI or AO channels
    • Analog output drifting, valve cannot keep stable position
    • Advant DCS reports AX670 module hardware fault alarm
    • Intermittent signal abnormality triggered by cabinet vibration

      Common root causes: ageing of analog conversion components, output driver circuit damage, gold‑plated edge‑connector contact oxidation, dust contamination.

  7. Pure maintenance‑oriented spare‑part component, only for repair and replacement of existing legacy Advant 500 / MOD300 DCS installations; not suitable for new‑project engineering deployment.

Typical Applications

  1. Spare‑part replacement for AX670 mixed analog I/O module inside ABB Advant500 / MOD300 DCS rack.
  2. On‑site troubleshooting scenarios: analog measuring channel failure, control valve output abnormality, AX670 module fault alarms.
  3. Preventive‑maintenance spare‑part inventory preparation for power plant, pulp‑paper, chemical legacy Advant DCS system.
  4. Hardware refurbishment for decommissioned Advant 500 controller assemblies.

Reviews

There are no reviews yet.

Be the first to review “ABB AX670 3BSE000566R1 Table Description:AX670, Mixed Analog I/O Module, 3BSE000566R1”

Your email address will not be published. Required fields are marked *