General Information
| Item | Specification |
|---|---|
| Part Number | CHBX01L, 2VAA008574R1 |
| Manufacturer | ABB |
| Product Family | ABB Ability Symphony Plus DCS, SD‑Series I/O System |
| Product Type | Compact Horizontal Bus Extender (Left‑side) for HN800 redundant I/O bus |
| Installation | DIN‑rail mounting, installed at the left end of horizontal SD‑Series I/O module row, paired with CHBX01R (right‑side bus extender) to form a complete I/O segment |
| Power Supply | 24 VDC auxiliary power (19.2‑30 VDC), feeds power to the whole horizontal I/O row via backplane bus |
| Lifecycle Status | Active product; OEM production, spare‑parts and technical support available. |
| ESD Handling Requirement | Bus interface electronic assembly; anti‑static wrist‑strap and anti‑static workstation required for installation and replacement. |
Electrical & Interface Specifications
- Backplane Interface: Redundant HN800 I/O bus connectors (A‑bus / B‑bus), high‑speed 4 MBit/s redundant I/O communication bus for SD‑series I/O modulesABB Abilit….
- Power Interface: 24 VDC power input terminals for supplying the entire horizontal I/O row.
- Mechanical Bus Interface: Internal row‑bus connector, cascades power and HN800 bus signals sequentially to every I/O module in the row.
- Signal Type: Redundant HN800 differential bus signals, 24 VDC module supply power distribution.
- On‑Board Circuitry: Bus termination circuitry, power distribution circuit, status LED indicators. No process I/O channels for field sensors/actuators.
- Bus Performance: HN800 bus baud rate 4 Mbit/s, dual redundant A/B bus for fault‑tolerant communicationABB Abilit….
- Power Consumption: Typical 2‑3 W (itself); distributes total row power for all I/O modules on this horizontal segment.
- Operation Limitation: Cannot operate standalone. Must be deployed together with CHBX01R, SD‑series I/O modules and Symphony Plus controller; defines the physical boundary of one horizontal I/O row segment.
- Compatibility Matrix
‑ Compatible System: ABB Symphony Plus SD‑Series DCS, HN800 redundant I/O bus system
‑ Matching Part: CHBX01R (Right‑side compact bus extender)
‑ Compatible I/O modules: All SD‑series SD I/O modules
‑ Hot‑swap: Not supported; power‑down the I/O row before replacement.
Environmental Specifications
| Item | Value |
|---|---|
| Operating Temperature | 0 °C ~ +55 °C inside ventilated control cabinet |
| Storage / Transport Temperature | ‑40 °C ~ +85 °C |
| Relative Humidity | 5‑95 % RH, non‑condensing |
| Compliance & Certifications | CE, UL, IEC 61010‑1 industrial automation standard |
| Protection Class | IP20 (module housing); internal circuit IP00 |
| Dimension | 125 mm × 45 mm × 110 mm (H×W×D) |
| Net Weight | Approx. 0.21 kg |
| Conformal Coating | Conformal‑coated variant available for harsh corrosive plant environments. |
| Vibration Resistance | Complies with IEC 60068‑2‑6 cabinet vibration criteria. |
Main Functions
- CHBX01L (2VAA008574R1) is the left‑side compact horizontal bus extender for ABB Symphony Plus SD‑Series HN800 redundant I/O bus. It is mounted at left end of a horizontal I/O row, working together with CHBX01R at right‑end to define one complete I/O bus segment.
- Provides physical termination for dual redundant HN800 A/B I/O bus, distributes 24 VDC auxiliary power supply to all I/O modules along this horizontal row via internal row‑backplane.
- Realizes high‑speed redundant HN800 bus communication between Symphony Plus controller and SD‑series field I/O modules; dual‑bus design improves communication reliability for critical power‑plant and process‑control applicationsABB Abilit….
- LED status indicators show power supply status and HN800 bus operating condition for on‑site inspection.
- No analog / digital field I/O channels; it is purely bus‑power distribution hardware, does not directly connect to field transmitters or actuators.
- Typical field failure symptoms
‑ Entire horizontal I/O row loss of power supply
‑ All modules on this row report HN800 bus communication fault
‑ Redundant bus single‑channel failure alarm
Common root causes: 24 VDC input power abnormality, backplane connector poor contact, bus termination hardware damage.
Typical Applications
- New‑project configuration and spare‑part replacement for Symphony Plus SD‑series HN800 I/O station left‑side bus extender.
- Power‑plant, pulp‑paper, chemical process DCS control cabinet I/O rack assembly.
- Preventive‑maintenance spare‑part inventory for ABB Symphony Plus DCS system.
- DCS system retrofit and expansion of SD‑series I/O stations.