ABB CI543 3BSE010699R1 Communication Interface Module

The CI543 3BSE010699R1 is rack‑mounted GCOM communication interface module for ABB Advant OCS / AC410 legacy DCS system. It realizes data interaction between Advant controller, operation station and field peripheral equipment, supports RS232‑C and RS485 physical interfaces, completes protocol conversion and transparent data transmission. This is discontinued legacy DCS spare‑part, mainly used for maintenance and spare‑part replacement of old petrochemical, power and metallurgy Advant OCS control cabinets. Not hot‑swappable.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware Electrical Specifications

‑ Power Supply:Supplied by rack back‑plane 24 VDC;typical power consumption 5.0 W

‑ Mechanical Structure:standard S100 rack plug‑in module;weight approx 0.45 kg

‑ On‑board Resources:serial protocol processing unit, signal driving circuit, data buffer unit, back‑plane bus interface, module self‑diagnosis circuit

‑ Communication Interface:internal back‑plane bus for data exchange with Advant controller;external RS‑232‑C / RS‑485 serial interface

‑ Galvanic Isolation:galvanic isolation between external serial‑port side and control internal logic side, isolation rating 2500 VAC

‑ Core Function:GCOM bus protocol processing, serial‑port protocol conversion, bidirectional data transmission between controller and external equipment

‑ Protection:serial‑port surge‑suppression and ESD protection

‑ Status LED Indicators:Power indicator, Module Fault indicator, communication sending‑receiving status LED

‑ Weight:approx 0.45 kg

Main Functions

‑ Installed in Advant OCS S100 standard rack, communicates with Advant AC410 series controller via rack back‑plane GCOM bus.

‑ Provides isolated RS‑232‑C and RS‑485 external serial channels, completes protocol conversion, realizes bidirectional data exchange between controller and upper‑level monitoring station, field instrument and third‑party equipment.

‑ Built‑in data buffer, adapts to multi‑point serial bus communication scene, reduces data‑loss risk caused by bus conflict.

‑ Module self‑diagnosis monitors back‑plane power‑supply and on‑board hardware status; detects hardware fault and communication abnormality, reports fault information to controller.

‑ Cannot run independently; must cooperate with Advant OCS rack and AC410 series controller. CI543 3BSE010699R1 belongs to dedicated GCOM communication board, cannot be substituted by general‑purpose serial communication modules.

Control & Monitoring Function

‑ Continuously monitors rack power‑supply and module hardware running state. Fault will activate panel fault LED and report fault alarm word to Advant controller.

‑ No local historical‑data storage; module status and fault codes need to be read through Advant configuration‑monitoring tool.

‑ Module hardware failure will cause loss of GCOM serial communication channel; controller internal logic operation keeps normal, but serial‑port data interaction with external equipment fails.

Signal Interfaces

‑ Back‑plane connector: inserts into S100 rack slot, connects to GCOM internal bus of Advant controller.

‑ External serial terminals: connect communication cables to operation station, field instruments and third‑party devices.

Environmental Specifications

‑ Mounting:insert into Advant OCS S100 standard rack slot

‑ Operating Temperature:‑20 ℃ ~ +60 ℃

‑ Storage Temperature:‑40 ℃ ~ +85 ℃

‑ Relative Humidity:5‑95 %RH, non‑condensing

‑ Protection Class:IP20, cabinet‑internal installation.

System Complementary Components
  1. CI543 GCOM communication interface module(3BSE010699R1)
Complementary parts: Advant OCS S100 rack, AC410 series controller, serial communication cables, Advant configuration monitoring tool.
Installation Notes

‑ Cut off control cabinet auxiliary power before inserting or replacing this module. Set serial‑port baud rate, data bit, parity bit according to site requirements; parameter mismatch will lead to communication no‑data.

‑ For spare‑part replacement: verify full model CI543 and part‑number 3BSE010699R1; after installation check back‑plane power‑supply, verify bidirectional data interaction between controller and external serial‑devices. Hardware‑version mismatch will bring risk of communication‑parsing abnormality.

‑ Module fault will result in failure of DCS system GCOM serial communication channel.

Typical Application Scenarios

Petrochemical, power, metallurgy old‑set Advant OCS DCS control cabinets; ABB Advant OCS system maintenance and spare‑part replacement; industrial spare‑part for GCOM bus serial‑communication gateway unit.

Key Features
  1. Advant OCS dedicated CI543 GCOM communication interface module (3BSE010699R1), completes protocol conversion and bidirectional data exchange between Advant controller and external serial‑port equipment.
  2. Isolated RS‑232‑C / RS‑485 dual physical interfaces, adapts to point‑to‑point and multi‑drop‑bus field wiring.
  3. Serial‑port galvanic‑isolation design, restrains field‑site electromagnetic interference and protects controller internal circuit.
  4. Built‑in data buffer, improves stability of multi‑node serial‑bus communication.
  5. Standard S100 rack plug‑in structure, convenient cabinet installation and spare‑part swapping.
  6. Legacy discontinued DCS spare‑part, only applied for old‑system maintenance and retrofit projects.

Reviews

There are no reviews yet.

Be the first to review “ABB CI543 3BSE010699R1 Communication Interface Module”

Your email address will not be published. Required fields are marked *