Description
‑ Power Supply:Supplied by S500 rack back‑plane 24 VDC;typical power consumption 5.0 W
‑ Mechanical Structure:standard S500 rack plug‑in module;weight approx 0.59 kg
‑ On‑board Resources:PROFIBUS DP‑V1 master‑station protocol processing unit, bus driving circuit, data buffer memory, CEX back‑plane bus controller, module self‑diagnosis circuit
‑ Communication Interface:internal CEX bus for data interaction with AC800M controller;single D‑Sub9 PROFIBUS DP‑V1 external bus interface
‑ Galvanic Isolation:galvanic isolation between PROFIBUS field‑bus side and controller internal logic side, isolation rating 2500 VAC
‑ Core Function:PROFIBUS DP‑V1 master‑station protocol processing, cyclic I/O data transmission, DP‑V1 acyclic parameter access, bus fault diagnosis, hot‑swap support
‑ Protection:bus‑port surge‑suppression and ESD protection
‑ Status LED Indicators:Power indicator, Module Fault indicator, PROFIBUS bus communication status LED
‑ Weight:approx 0.59 kg
‑ Installed in S500 standard rack, communicates with AC800M series controller via rack internal CEX bus. Multiple CI854 modules can be arranged on one CEX bus to expand system PROFIBUS network quantity.
‑ Operates as PROFIBUS DP‑V1 master node, supports baud rate from 9.6 kbit/s up to 12 Mbit/s. Cyclically sends control output commands to field PROFIBUS slave‑station equipment, collects process feedback data from slave stations. Supports DP‑V1 acyclic service for equipment parameter configuration and fault diagnosis reading.
‑ Built‑in data buffer improves bus communication stability under multi‑node networking condition, reduces data loss risk. Supports hot‑swap, module can be replaced without rack power‑off during maintenance.
‑ Module self‑diagnosis monitors back‑plane power‑supply and on‑board hardware integrity; detects hardware fault, bus short‑circuit and bus‑off fault, reports fault word to AC800M controller.
‑ Cannot run independently; must cooperate with S500 rack and AC800M series controller. CI854 3BSE025347R1 is dedicated PROFIBUS DP‑V1 master‑station communication board, cannot be substituted by general‑purpose PROFIBUS communication modules。
‑ Continuously monitors rack power‑supply and module hardware running state. Fault will activate panel fault LED and report fault alarm word to AC800M controller.
‑ No local historical‑data storage; module status and fault codes need to be read through Control Builder configuration‑monitoring tool.
‑ Module hardware failure will cause this PROFIBUS DP bus breakdown; controller internal logic keeps normal operation, but all PROFIBUS slave devices under this bus lose communication, field data acquisition and control output fail.
‑ Back‑plane connector: inserts into S500 rack slot, connects to CEX internal bus of AC800M controller.
‑ External D‑Sub9 connector: connect standard PROFIBUS shielded bus cables to each field PROFIBUS DP‑V1 slave‑station equipment.
‑ Mounting:insert into S500 standard rack slot
‑ Operating Temperature:‑20 ℃ ~ +60 ℃
‑ Storage Temperature:‑40 ℃ ~ +85 ℃
‑ Relative Humidity:5‑95 %RH, non‑condensing
‑ Protection Class:IP20, cabinet‑internal installation.
- CI854 PROFIBUS DP‑V1 master communication interface module(3BSE025347R1)
Complementary parts: S500 rack, AC800M series controller, PROFIBUS DP shielded communication cables, field PROFIBUS slave‑station devices, Control Builder configuration monitoring tool.
‑ Cut off control cabinet auxiliary power before inserting or replacing this module, although module supports hot‑swap, power‑off operation is recommended for spare‑part replacement. Set PROFIBUS bus baud rate, slave station address list according to site network requirements, install terminal resistor at both ends of PROFIBUS bus trunk.
‑ For spare‑part replacement: verify full model CI854 and part‑number 3BSE025347R1; after installation check back‑plane power‑supply, verify cyclic data interaction between controller and each PROFIBUS DP‑V1 slave‑station. Hardware‑version mismatch will bring risk of bus communication parsing abnormality.
‑ Module fault will result in total communication failure of all slave devices on corresponding PROFIBUS DP network.
Power, petrochemical, metallurgy old‑set AC800M /800xA DCS control cabinets; ABB 800xA system maintenance and spare‑part replacement; industrial spare‑part for PROFIBUS DP‑V1 master‑station communication gateway unit.
- AC800M dedicated CI854 PROFIBUS DP‑V1 master communication interface module (3BSE025347R1), realizes AC800M working as PROFIBUS master node for data interaction with multiple field slave‑station devices.
- Supports full‑range PROFIBUS baud rate, supports DP‑V1 acyclic diagnosis and parameter access function.
- Bus‑port galvanic‑isolation design, restrains field‑site electromagnetic interference and protects controller internal circuit.
- Supports hot‑swap, convenient for field maintenance and spare‑part swapping.
- Standard S500 rack plug‑in structure, convenient cabinet installation.
- Legacy discontinued DCS spare‑part, only applied for old‑system maintenance and retrofit projects。






Reviews