ABB CI854K01 3BSE025961R1 Master Communication Interface Kit

The CI854K01 3BSE025961R1 is S500 rack‑mount plug‑in PROFIBUS DP‑V1 master communication complete kit for ABB AC800M / 800xA DCS system, including CI854 module body and TP854 baseplate. It is the early‑generation PROFIBUS DP‑V1 master station unit, equipped with single D‑Sub9 PROFIBUS interface, no line‑redundancy function. It acts as PROFIBUS DP‑V1 master station, connects AC800M controller to field PROFIBUS slave‑station devices including distributed I/O, frequency converters, transmitters and actuators, realizes cyclic I/O data exchange and DP‑V1 acyclic parameter diagnosis access. This is discontinued legacy DCS spare‑part, widely used for maintenance replacement of old power, petrochemical and metallurgy automation control cabinets. It supports hot‑swap function。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware Electrical Specifications

‑ Power Supply:Supplied by S500 rack back‑plane 24 VDC;typical power consumption 5.0 W

‑ Mechanical Structure:standard S500 rack plug‑in module, matched with TP854 baseplate;overall weight approx 0.58 kg

‑ On‑board Resources:PROFIBUS DP‑V1 master‑station protocol processing unit, single‑channel bus driving circuit, data buffer memory, CEX back‑plane bus controller, module self‑diagnosis circuit

‑ Communication Interface:internal CEX bus for data interaction with AC800M controller;single D‑Sub9 female PROFIBUS DP‑V1 external bus interface, no redundant channel

‑ Galvanic Isolation:galvanic isolation between PROFIBUS field‑bus side and controller internal logic side, isolation rating 2500 VAC

‑ Core Function:PROFIBUS DP‑V1 master‑station protocol processing, cyclic I/O data transmission, DP‑V1 acyclic parameter access, bus fault diagnosis, hot‑swap support

‑ Protection:bus‑port surge‑suppression and ESD protection

‑ Status LED Indicators:Power indicator, Module Fault indicator, PROFIBUS bus communication status LED

‑ Weight:approx 0.58 kg

Main Functions

‑ Installed in S500 standard rack via TP854 baseplate, communicates with AC800M series controller via rack internal CEX bus. Maximum 12 CI854K01 modules can be arranged on one CEX bus to expand PROFIBUS network quantity.

‑ Operates as PROFIBUS DP‑V1 master node, supports baud rate from 9.6 kbit/s up to 12 Mbit/s. No dual‑cable line‑redundancy function. Cyclically sends control output commands to field PROFIBUS slave‑station equipment, collects process feedback data from slave stations. Supports DP‑V1 acyclic service for equipment parameter configuration and fault diagnosis reading. Single bus segment supports up to 32 slave nodes, expandable by repeaters, maximum 124 slaves for one CI854K01 moduleManualsLib。

‑ Built‑in data buffer improves bus communication stability under multi‑node networking condition, reduces data loss risk. Supports hot‑swap, module can be replaced without rack power‑off during maintenance.

‑ Module self‑diagnosis monitors back‑plane power‑supply and on‑board hardware integrity; detects hardware fault, bus short‑circuit and bus‑off fault, reports fault word to AC800M controller.

‑ Cannot run independently; must cooperate with S500 rack, TP854 baseplate and AC800M series controller. CI854K01 3BSE025961R1 is early‑generation dedicated PROFIBUS DP‑V1 master‑station communication board, cannot be substituted by general‑purpose PROFIBUS communication modules.

Control & Monitoring Function

‑ Continuously monitors rack power‑supply and module hardware running state. Fault will activate panel fault LED and report fault alarm word to AC800M controller.

‑ No local historical‑data storage; module status and fault codes need to be read through Control Builder configuration‑monitoring tool.

‑ Module hardware failure will cause this PROFIBUS DP bus breakdown; controller internal logic keeps normal operation, but all PROFIBUS slave devices under this bus lose communication, field data acquisition and control output fail.

Signal Interfaces

‑ Back‑plane connector: inserts into S500 rack slot via TP854 baseplate, connects to CEX internal bus of AC800M controller.

‑ External single D‑Sub9 female connector: connect standard PROFIBUS shielded bus cables to each field PROFIBUS DP‑V1 slave‑station equipment.

Environmental Specifications

‑ Mounting:insert into S500 standard rack slot with TP854 baseplate

‑ Operating Temperature:‑20 ℃ ~ +60 ℃

‑ Storage Temperature:‑40 ℃ ~ +85 ℃

‑ Relative Humidity:5‑95 %RH, non‑condensing

‑ Pollution degree:Degree 2

‑ Protection Class:IP20, cabinet‑internal installation.

System Complementary Components
  1. CI854K01 PROFIBUS DP‑V1 master communication interface kit(3BSE025961R1)
Complementary parts: S500 rack, TP854 baseplate, AC800M series controller, PROFIBUS DP shielded communication cables, field PROFIBUS DP‑V1 slave‑station devices, Control Builder configuration monitoring tool.
Installation Notes

‑ Cut off control cabinet auxiliary power before inserting or replacing this module, although module supports hot‑swap, power‑off operation is recommended for spare‑part replacement. Set PROFIBUS bus baud rate, slave station address list according to site network requirements, install terminal resistor at both ends of PROFIBUS bus trunk. This hardware has no line‑redundancy function, cannot match dual‑cable redundant bus layout. It is recommended to replace module together with TP854 baseplate for spare‑part maintenance.

‑ For spare‑part replacement: verify full model CI854K01 and part‑number 3BSE025961R1; after installation check back‑plane power‑supply, verify cyclic data interaction between controller and each PROFIBUS DP‑V1 slave‑station. Hardware‑version mismatch will bring risk of bus communication parsing abnormality.

‑ Module fault will result in total communication failure of all slave devices on corresponding PROFIBUS DP network.

Typical Application Scenarios

Power, petrochemical, metallurgy old‑set AC800M /800xA DCS control cabinets; ABB 800xA system maintenance and spare‑part replacement; industrial spare‑part for standard PROFIBUS DP‑V1 master‑station communication gateway unit.

Key Features
  1. AC800M dedicated CI854K01 PROFIBUS DP‑V1 master communication interface kit (3BSE025961R1), early‑generation master‑station solution, realizes AC800M working as PROFIBUS master node for data interaction with multiple field slave‑station devices, supplied matched with TP854 baseplate, without line‑redundancy capability.
  2. Supports full‑range PROFIBUS baud rate, supports DP‑V1 acyclic diagnosis and parameter access function.
  3. Bus‑port galvanic‑isolation design, restrains field‑site electromagnetic interference and protects controller internal circuit.
  4. Supports hot‑swap, convenient for field maintenance and spare‑part swapping.
  5. Standard S500 rack plug‑in structure, convenient cabinet installation.
  6. Legacy discontinued DCS spare‑part, only applied for old‑system maintenance and retrofit projects。

Reviews

There are no reviews yet.

Be the first to review “ABB CI854K01 3BSE025961R1 Master Communication Interface Kit”

Your email address will not be published. Required fields are marked *