Description
Hardware & Electrical Specifications
- Model:DYPS154C
- Part Number:61430001‑YP
- Module Type:Solid‑state MOSFET digital output module (sink type)
- Channel count:16 output channels
- Isolation architecture:Every 4 channels form one isolated group; opto‑coupler galvanic isolation between groups; isolation between field circuit and back‑plane logic bus
- Field load voltage:DC 12 V ~ 30 V
- Per‑channel continuous output current:1 A DC
- Per‑channel peak current:3 A, maximum duration ≤100 ms
- Total maximum module load current:8 A (all 16 channels activated simultaneously)
- Output response time:≤100 μs
- Typical on‑state resistance:≤0.1 Ω
- Channel‑level protection:
- Over‑current limiting:1.2 A ±0.1 A, auto‑recovery after fault removal
- Short‑circuit protection:tolerate continuous short‑circuit, no hardware damage, auto‑reset
- Reverse‑polarity protection:tolerate reverse DC 30 V wiring
- Over‑voltage clamping:max transient 36 V DC
- Logic power supply:24 V DC supplied by rack back‑plane
- Max power consumption:4.8 W
- Insulation strength:2500 V AC between field side and logic back‑plane side
- Insulation resistance:>100 MΩ @ 500 V DC
Environmental Specifications
- Operating temperature:0 ℃ ~ +55 ℃
- Storage temperature:‑20 ℃ ~ +70 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:IP20 (inside control cabinet)
- EMC compliance:IEC 61000‑6‑2 industrial immunity standard
- Certifications:CE
Mechanical Data
- Installation:Plug‑in slot mounting on Advant OCS standard rack, mechanical latch locking
- Terminal:Screw‑type removable terminal block, suitable for 0.75 mm²‑2.5 mm² copper conductors
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:120 mm × 110 mm × 45 mm
- Weight:approx 0.33 kg
Main Functions
- 16‑channel solid‑state DC output:MOSFET sink output, no mechanical contact abrasion, support frequent high‑speed switching. Drive DC solenoid valves, small intermediate relays, cabinet indicator lamps, alarm buzzers, field proximity sensor power supply loads。
- Group‑wise galvanic isolation:4 channels per isolation group, effectively suppress cross‑group interference when mixing different field power domains.
- Full channel self‑diagnosis:Detect output short‑circuit, over‑current, load open‑circuit, internal circuit fault. Fault code with channel number is uploaded to DCS controller for alarm.
- Per‑channel LED status indicator
- Green ON:output channel activated
- Green OFF:output channel de‑activated
- Red flash:channel fault (short‑circuit / over‑current / open‑load)
- Software configurable parameters via Control Builder:output invert logic, fault latch / auto‑reset mode, open‑circuit diagnosis enable / disable.
- Auto‑recovery protection:No fuse required; after short‑circuit or over‑current fault disappears, channel automatically resumes operation without module replacement, reduce maintenance workload。
Installation & Wiring Requirements
- Insert into Advant OCS standard rack slot, lock mechanical latch; back‑plane bus completes power supply and communication automatically.
- Maintain cabinet ventilation, avoid conductive dust, corrosive gas and strong electromagnetic field.
- For inductive DC loads (solenoid coil, relay coil), connect free‑wheeling diode in parallel at load side to absorb back‑EMF, protect MOSFET output circuit.
- Strictly follow current rating: single channel shall not exceed 1 A continuous current; total module load shall not exceed 8 A.
- Cabinet protective grounding must comply with industrial control grounding specification to guarantee isolation performance and anti‑interference capability.
- Do not apply AC voltage to output channels, this module is only for DC load application.