Description
Hardware & Electrical Specifications
- Model:DYSF118B
- Part Number:61430001‑XG
- Module Type:Analog Output Module
- Channel count:8 channels, each channel software‑selectable current / voltage output
- Isolation architecture:Every 2 channels form one isolated group; opto‑coupler galvanic isolation between groups; galvanic isolation between field circuit and back‑plane logic bus
- Output signal ranges (per‑channel configurable):
- Current:4‑20 mA DC, 0‑20 mA DC
- Voltage:0‑10 V DC, 1‑5 V DC
- Load requirement:
- Current output:max load resistance 1000 Ω
- Voltage output:min load resistance ≥10 kΩ
- DAC Resolution:16‑bit
- Output Accuracy:
- ±0.05 % FS @ 25 ℃±5 ℃
- ±0.10 % FS over full operating temperature range
- Temperature drift:≤50 ppm/℃
- Settling response time:≤1 ms (output reach final value within tolerance band)
- Channel‑level electronic protection:
- Over‑current limit:max 25 mA continuous per channel, auto current limiting
- Over‑voltage clamping:±36 V DC transient protection
- Short‑circuit withstand:tolerate continuous output short‑circuit, auto‑recovery after fault removal
- Reverse‑polarity withstand:‑30 V DC reverse wiring protection
- Logic power supply:24 V DC supplied by rack back‑plane
- Max power consumption:5.0 W
- Dielectric strength:2500 V AC between field side and back‑plane logic side
- Insulation resistance:>100 MΩ @ 500 V DC
Environmental Specifications
- Operating temperature:0 ℃ ~ +55 ℃
- Storage temperature:‑20 ℃ ~ +70 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:IP20 (module inside control cabinet)
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Plug‑in slot mounting on Advant OCS standard rack, mechanical latch locking
- Terminal:Removable screw terminal block
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:120 mm × 110 mm × 45 mm
- Weight:approx 0.34 kg
Main Functions
- 8‑channel multi‑range analog output:Each channel independently switch between current and voltage mode, adapt to different field modulating actuators such as regulating valve positioner, frequency converter, analog display instrument.
- Group‑wise galvanic isolation:2 channels per isolation group, suppress ground loop interference when different field ground domains are mixed.
- Full channel self‑diagnosis function:Detect output short‑circuit, over‑current, open‑load, internal DAC hardware fault. Fault information including channel number and fault type is uploaded to DCS controller for alarm log.
- Per‑channel LED status indicator
- Green ON:channel normal running
- Green OFF:channel deactivated
- Red flash:channel fault (short‑circuit / over‑current / open‑circuit / hardware failure)
- Parameter configuration via Control Builder software:Select output signal range, output fail‑safe value (hold last value / preset safe value), fault latch / auto‑reset mode, channel signal invert.
- Fail‑safe feature:When communication loss between module and controller occurs, each channel can hold last output value or jump to user‑defined safe output value, guarantee process safety.
- No field‑side fuse required:Adopt electronic limiting and short‑circuit protection, automatically restore operation after fault condition disappears, reduce spare‑part maintenance work.
Installation & Wiring Requirements
- Insert module into Advant OCS standard rack slot, lock mechanical latch; back‑plane bus completes power supply and ModuleBus communication automatically.
- Ensure cabinet ventilation, avoid conductive dust, corrosive gas and strong electromagnetic interference source nearby.
- Use shielded twisted‑pair cable for analog output wiring; connect cable shield single‑end grounding at cabinet side to reduce noise interference.
- Strictly follow load specification: do not exceed max load resistance for current output, do not connect low‑impedance load to voltage output channel.
- Cabinet protective grounding must comply with industrial control grounding specification to guarantee isolation performance and anti‑interference capability.
- Do not mix high‑voltage AC signal wiring together with analog output signal cable.