Description
Hardware & Electrical Specifications
- Model:DYTP123A
- Part Number:61430001‑TW
- Module Type:Digital Input Module
- Channel count:16 input channels
- Isolation architecture:Every 4 channels form one isolated group; opto‑coupler galvanic isolation between groups; full galvanic isolation between field circuit and back‑plane logic bus
- Input signal type:Dry‑contact / Wet‑contact 24 VDC sink/source configurable
- Input threshold level:
- ON threshold:≥15 V DC
- OFF threshold:≤5 V DC
- Rated field input voltage:24 V DC (‑15% ~ +10%)
- Input current per channel:approx 7 mA @24 V DC
- Input filter:Hardware RC debounce filter, filter time configurable by software (0.5‑20 ms)
- Channel‑level protection:
- Over‑voltage transient clamping
- Reverse‑polarity wiring withstand
- Surge protection comply with IEC 61000‑4‑5
- Logic power supply:24 V DC supplied by rack back‑plane
- Max power consumption:4.5 W
- Dielectric strength:2500 V AC 1 min between field side and logic back‑plane side
- Insulation resistance:>100 MΩ @ 500 V DC
Environmental Specifications
- Operating temperature:0 ℃ ~ +55 ℃
- Storage temperature:‑20 ℃ ~ +70 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:IP20 (module inside control cabinet)
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Plug‑in slot mounting on Advant OCS standard rack, mechanical latch locking
- Terminal:Removable screw‑type terminal block
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:120 mm × 110 mm × 45 mm
- Weight:approx 0.35 kg
Main Functions
- 16‑channel digital signal acquisition:Support dry‑contact and wet 24 VDC input, collect status of auxiliary contacts of circuit‑breakers, valves, limit switches, proximity switches and relay feedback signals.
- Group‑wise galvanic isolation:4 channels per isolation group, effectively eliminate ground‑loop interference when connecting field devices with different grounding reference points.
- Hardware & software debounce filter:Hardware RC filter plus software configurable debounce time, eliminate contact bounce interference from mechanical contacts, avoid false signal flipping.
- Full channel self‑diagnosis function:Detect field circuit open‑circuit, abnormal input voltage, internal circuit fault. Fault information with channel number is uploaded to DCS controller for alarm log.
- Per‑channel LED status indicator
- Green ON:Input channel logic‑high
- Green OFF:Input channel logic‑low
- Red flash:Channel fault status
- Parameter configuration via Control Builder software:Input polarity inversion setting, debounce time adjustment, diagnosis function enable/disable, fault latch / auto‑reset mode.
- Hot‑swap support:Module can be plugged and pulled out online without powering off the rack, convenient for maintenance and replacement.
Installation & Wiring Requirements
- Insert module into Advant OCS standard rack slot, lock mechanical latch; back‑plane bus completes power supply and ModuleBus communication automatically.
- Ensure cabinet ventilation, avoid conductive dust, corrosive gas and strong electromagnetic interference source nearby.
- Separate digital‑input signal cables from high‑voltage AC power cables, keep wiring distance to reduce interference coupling.
- For dry‑contact input application, external 24 VDC power supply shall meet power‑rating requirement; do not mix different potential power domains inside one isolation group.
- Cabinet protective grounding must comply with industrial control grounding specification to guarantee isolation performance and anti‑interference capability.
- Check input voltage shall not exceed 30 V DC maximum rating to prevent module damage.


-300x300.jpg)
-300x300.jpg)

Reviews
There are no reviews yet.