Description
‑ Power Supply:21.6‑27.0 VDC,typical 24 VDC;consumption 540 mA@24VDC
‑ Mechanical Structure:panel flush‑mount housing;dimension 72 mm × 144 mm × 381 mm;weight approx 1.25 kg
‑ On‑board Resources:analog input conditioning circuit, D/A conversion unit, serial communication interface, plasma bar‑graph drive, keyboard scanning logic, self‑diagnosis circuit
‑ Communication Interface:5 kHz / 40 kHz serial link, connect to Harmony termination module NICS01 / NTCS04
‑ Galvanic Isolation:signal‑side and logic‑side galvanic isolation
‑ Signal Types:analog process‑variable input;analog control‑output;set‑point internal calculation
‑ Display:3‑channel high‑resolution gas plasma bar‑graph for process variable, set‑point, output value;8‑character alphanumeric display for value, mode, alarm and fault code
‑ Operation Mode:Auto / Manual / Cascade control mode switch via front‑panel membrane keys
‑ Protection:input surge suppression, signal over‑range detection
‑ Status LED:power indicator, fault/alarm indicator
‑ Weight:approx 1.25 kg
‑ Realizes single‑loop man‑machine operation interface for Harmony DCS: displays process variable, set‑point and control output value via bar‑graph and character screen.
‑ Supports mode switching between automatic, manual and cascade; operator can modify set‑point and manually adjust output locally.
‑ Receives process analog signal, supports square‑root processing for flow measurement application.
‑ Communicates with Harmony controller through serial bus, exchanges loop parameters, operation commands and alarm information.
‑ Local alarm indication for process over‑range and station hardware fault.
‑ Module self‑diagnosis monitors power supply, communication link and internal hardware, reports fault status to upper controller.
‑ Cannot run independently; must cooperate with corresponding termination I/O modules (NICS01, NTCS04 etc.) and Harmony controller. IISAC01 belongs to legacy DCS hardware, pin‑compatible only within same series, cannot substitute other control‑station models directly.
‑ Continuously monitors power supply, serial communication link and internal hardware health; faults will trigger local alarm and send fault word to DCS controller.
‑ No local storage for historical data; parameters and fault information are read via upper‑level DCS system.
‑ Module hardware failure will cause loss of local loop operation function; DCS remote automatic control can still work if controller side is intact, but on‑site manual intervention is unavailable.
‑ Serial link interface: connect to NICS01 / NTCS04 termination module for data exchange with Harmony controller.
‑ Mounting:panel flush mounting
‑ Operating Temperature:‑10 ℃ ~ +55 ℃
‑ Storage Temperature:‑40 ℃ ~ +70 ℃
‑ Relative Humidity:5‑95 %RH, non‑condensing
‑ Protection Class:front‑panel meets local panel‑mount requirement, rear side inside cabinet.
- IISAC01 analog control station
Complementary parts: Harmony DCS controller, NICS01 / NTCS04 termination I/O module, serial link cable, DCS configuration software.
‑ Panel cut‑out dimension shall comply with specification; wiring must follow DCS drawing, distinguish signal loop and power supply loop.
‑ For spare‑part replacement: verify model IISAC01; after installation check serial communication link, verify display, mode switch, set‑point and manual output function. Mismatched hardware version may cause communication failure or display anomaly.
‑ Module fault will result in loss of local operator control for corresponding control loop.
Thermal‑power plant, chemical and petro‑chemical process control; ABB Harmony legacy DCS system; industrial spare‑part for single‑loop local operator‑station unit.
- Harmony DCS dedicated IISAC01 analog control station, provides single‑loop local man‑machine operation, display and manual‑auto switching function for process loop control.
- High‑resolution plasma bar‑graph plus alphanumeric display, intuitive for on‑site operator observation and operation.
- Supports square‑root function for flow measurement scenario.
- Serial bus communication with Harmony controller, complete local‑remote coordination control.
- Panel‑mount structure for field control cabinet installation.





-300x300.jpg)
Reviews
There are no reviews yet.