Description
‑ Power Supply:15 VDC from PCU card rack backplane;typical power consumption 7.2 W
‑ Mechanical Structure:standard INFI‑90 PCU slot plug‑in module;front‑panel handle locking structure;weight approx 0.85 kg
‑ On‑board Resources:INFI‑NET bus interface unit, computer communication driving circuit, data buffer memory, module self‑diagnosis circuit
‑ Communication Interface:INFI‑NET high‑speed serial loop interface;computer side ICI communication interface
‑ Galvanic Isolation:galvanic isolation between INFI‑NET network side and computer communication side, isolation rating 2500 VAC
‑ Core Function:protocol conversion, data buffering, bidirectional data transmission between INFI‑NET loop and external computer
‑ Protection:bus surge‑suppression, communication signal over‑range monitoring
‑ Status LED Indicators:Power indicator, Module Fault indicator, network communication status LED, computer link status LED
‑ Weight:approx 0.85 kg
‑ Connects to INFI‑NET control loop via cooperating with INNIS01 module, receives process data, alarm information and controller parameters from DCS network, forwards to external host computer.
‑ Transmits upper‑level computer issuing commands, set‑point values and configuration download data to INFI‑NET DCS control nodes.
‑ Implements data buffer processing, reduces communication conflict of high‑speed loop, guarantees stable data interaction between computer and DCS system.
‑ Module self‑diagnosis monitors back‑plane power supply, INFI‑NET bus link, computer communication channel and on‑board hardware status; detects signal loss, communication interruption and hardware fault, reports fault status to DCS system.
‑ Cannot run independently; must be matched with INNIS01 network interface slave module and INFI‑90 PCU rack. INICT01 belongs to legacy DCS hardware, only compatible with INFI‑90 / Symphony‑Harmony system, cannot be used for other series DCS.
‑ Continuously monitors back‑plane power, INFI‑NET bus communication, computer link and internal hardware health. Detected faults activate fault LED and report fault word to DCS controller.
‑ No local historical‑data storage; module status and fault codes are read through DCS system or commissioning tool.
‑ Module hardware failure will cause loss of communication channel between INFI‑NET loop and external computer; DCS internal control loop still runs normally, but upper‑computer cannot exchange data with DCS via this channel.
‑ Back‑plane connector: inserts into INFI‑90 PCU rack slot, connects to INNIS01 module through rack internal bus.
‑ Computer communication interface: connects to external host computer equipment.
‑ Mounting:insert into standard INFI‑90 PCU card rack slot
‑ Operating Temperature:‑10 ℃ ~ +60 ℃
‑ Storage Temperature:‑40 ℃ ~ +70 ℃
‑ Relative Humidity:5‑95 %RH, non‑condensing
‑ Protection Class:IP20, for cabinet‑internal installation.
- INICT01 INFI‑NET computer transfer module
Complementary parts: INFI‑90 PCU card rack, INNIS01 network interface slave module, INFI‑NET communication cable, upper‑level host computer.
‑ Power off PCU rack before inserting or removing this module. Ensure matching with INNIS01 module, incorrect module collocation will lead to communication failure.
‑ For spare‑part replacement: verify model INICT01; after installation, check back‑plane power supply, INFI‑NET‑loop communication and computer‑host data interaction function. Hardware version mismatch will cause communication abnormality.
‑ Module fault results in failure of data exchange between DCS INFI‑‑NET loop and external computer.
Thermal‑power plant, chemical‑plant legacy control system; ABB Bailey INFI‑90 / Symphony‑Harmony DCS; industrial spare‑part for DCS‑to‑computer communication interface unit.
- INFI‑90 DCS dedicated INICT01 computer transfer module, realizes bidirectional data‑exchange between INFI‑NET high‑speed control loop and external host computer, hardware variant INICT01.
- Standard PCU rack plug‑in structure, convenient for cabinet installation and spare‑part replacement.
- Built‑in data buffer function, improves stability of high‑speed network communication.
- Complete self‑diagnosis function for network link and hardware, convenient for on‑site communication‑fault location.
- Legacy discontinued DCS component, mainly applied in old‑system maintenance and retrofit projects.