Description
‑ Power Supply:Power supplied by Harmony rack back‑plane, 5VDC back‑plane power supply
‑ Mechanical Structure:Rack plug‑in module for Symphony Harmony rack;overall weight approx 0.34kg
‑ On‑board Resources:INFI‑NET signal transformer isolation circuit, ring‑network terminal matching resistance, surge suppression protection circuit, link state detection circuit.
‑ Communication Interface:Two groups of INFI‑NET dual‑ring coaxial external interfaces; internal rack back‑plane bus connects with processor/gateway module.
‑ Galvanic Isolation:Transformer‑type isolation between external coaxial ring‑network side and rack internal system side.
‑ Core Function:INFI‑NET dual‑ring network physical signal termination, coaxial cable impedance matching, signal isolation, surge protection, ring link status detection, complete physical connection between rack internal modules and INFI‑NET ring network.
‑ Protection:Coaxial port surge and over‑voltage protection.
‑ Status LED Indicators:Ring A communication LED, Ring B communication LED, fault status LED.
‑ Weight:approx 0.34kg
‑ INIIT13 is physical interface termination unit of INFI‑NET dual redundant ring network. Each station must be equipped with INIIT13 to access INFI‑NET ring. Two independent ring channels Ring A and Ring B realize dual‑ring redundancy.
‑ Built‑in precise impedance matching circuit for coaxial cable, guarantee signal integrity of INFI‑NET high‑speed ring communication, restrain signal reflection distortion. Transformer isolation isolates external ring‑network interference from rack internal system circuit.
‑ Detect link status of Ring A and Ring B in real‑time. When ring break, cable fault or signal abnormality occurs, LED gives indication and upload fault alarm information to DCS operator station.
‑ Installed on Symphony Harmony standard rack, communicate with station processor or INICT03A gateway module via back‑plane bus, cannot work independently without matching ring‑network coaxial cable.
Difference compared with INIIT02:INIIT13 is upgraded dual‑ring termination module, better anti‑surge performance; INIIT02 is early‑generation INFI‑NET termination unit.
‑ Process physical‑layer signal of INFI‑NET dual‑ring network, provide impedance matching and isolation protection.
‑ Monitor Ring A / Ring B link running status, ring break fault information upload to DCS system.
‑ No data protocol parsing and no process control logic function.
‑ Back‑plane:Rack internal back‑plane bus, interact with station processor or gateway module.
‑ External interfaces:Two groups INFI‑NET coaxial connectors for Ring A and Ring B ring‑network wiring.
‑ Mounting:Plug‑in installation on Symphony Harmony standard rack
‑ Operating Temperature:‑20 ℃ ~ +60 ℃
‑ Storage Temperature:‑40 ℃ ~ +85 ℃
‑ Relative Humidity:5‑95 %RH, non‑condensing
‑ Pollution degree:Degree 2
‑ Protection Class:IP20, cabinet‑internal installation.
- INIIT13 INFI‑NET interface termination module(3BSE008592R1)
Complementary parts: Symphony Harmony rack, INFI‑NET coaxial communication cable, IMMFP03 / BRC series processor, INICT03A gateway module, system rack power supply, operator station.
‑ Insert module into dedicated INFI‑NET slot of Harmony rack, tighten front‑panel screws to ensure reliable back‑plane connector contact.
‑ Strictly distinguish Ring A and Ring B coaxial ports, follow ring‑network wiring sequence; coaxial connectors shall be fastened tightly, loose connectors easily cause ring‑network communication jitter or ring break.
‑ Module replacement recommends power‑off operation. After replacement, check Ring A and Ring B LED status, confirm INFI‑NET dual‑ring network no ring‑break alarm, verify cross‑station data exchange normal.
‑ Do not short‑circuit coaxial core wire and shielding layer, avoid module hardware burnout.
Power plant, petrochemical, pulp‑and‑paper industry Symphony INFI90 DCS control cabinets; physical termination spare‑part for INFI‑NET dual redundant ring network.
- ABB Symphony Harmony INIIT13 INFI‑NET interface termination module (3BSE008592R1), physical‑layer termination unit for INFI‑NET dual‑ring network.
- Dual independent Ring A / Ring B channel, built‑in impedance matching, transformer isolation and surge suppression for coaxial ring‑network signal.
- Real‑time dual‑ring link monitoring, ring‑break fault LED indication and alarm upload function.
- Rack plug‑in structure, cabinet‑internal IP20 application, each INFI90 control station needs to configure this module to access ring network.
- Only physical‑layer signal processing, no protocol parsing and control logic.
- Discontinued legacy DCS spare‑part, used for old‑system maintenance and retrofit projects。