Description
‑ Power Supply:Powered via PCU rack back‑plane, +5 VDC;typical power consumption 2.1 W
‑ Mechanical Structure:standard INFI‑90 PCU slot plug‑in module, front‑panel locking handle;weight approx 0.82 kg
‑ On‑board Resources:serial port driving circuit, optical isolation unit, jumper configuration circuit, back‑plane bus interface, module self‑diagnosis circuit
‑ Communication Interface:two RS‑232‑C optically‑isolated interfaces;one port configurable for RS‑485;internal back‑plane interface connecting to MFP processor
‑ Galvanic Isolation:galvanic isolation for serial communication ports, isolation rating 2500 VAC
‑ Core Function:serial signal termination, electrical isolation, physical interface conversion between MFP processor and external serial devices
‑ Protection:serial‑port surge‑suppression protection
‑ Status LED Indicators:Power indicator, Module Fault indicator, communication channel status LED
‑ Weight:approx 0.82 kg
‑ Matches with IMMFP series multi‑function processor, provides physical serial interface channel for DCS controller.
‑ Supports connection to analog control stations (IISAC01), upper‑level host computer, printer and sequence‑of‑event recording equipment via RS‑232‑C / RS‑485 serial link.
‑ Hardware jumper selection: one channel can switch between RS‑232‑C isolated mode and RS‑485 non‑isolated mode for multi‑drop bus connection.
‑ Provides electrical isolation between controller internal logic and external serial equipment, suppresses field electromagnetic interference.
‑ Module self‑diagnosis monitors back‑plane power supply and hardware circuit, reports fault status to MFP processor.
‑ Cannot run independently; must cooperate with MFP multi‑function processor and INFI‑90 PCU rack. NIMP01 belongs to legacy DCS hardware, only compatible with INFI‑90 / Symphony‑Harmony system.
‑ Continuously monitors back‑plane power supply and on‑board hardware status. Fault will trigger fault LED and report fault word to MFP processor.
‑ No local historical‑data storage; module status and fault codes are read through DCS system or commissioning tool.
‑ Module hardware failure will cause loss of external serial communication channel of corresponding MFP processor; DCS internal control logic still runs normally.
‑ Back‑plane connector: inserts into PCU rack slot, communicates with IMMFP multi‑function processor via rack internal bus.
‑ Front‑panel serial ports: RS‑232‑C / RS‑485 interfaces for connecting external field devices.
‑ Mounting:insert into standard INFI‑90 PCU card rack slot
‑ Operating Temperature:‑10 ℃ ~ +60 ℃
‑ Storage Temperature:‑40 ℃ ~ +70 ℃
‑ Relative Humidity:5‑95 %RH, non‑condensing
‑ Protection Class:IP20, cabinet‑internal installation.
- NIMP01 multi‑function processor termination module
Complementary parts: INFI‑90 PCU card rack, IMMFPxx multi‑function processor, serial communication cables, external serial devices (control station, host computer, printer).
‑ Power off PCU rack before inserting or removing this module. Set hardware jumpers according to actual communication mode (RS‑232‑C / RS‑485). Incorrect jumper setting will lead to communication failure.
‑ For spare‑part replacement: verify model NIMP01; after installation check back‑plane power supply, verify serial‑port data interaction with external equipment. Hardware version mismatch may cause communication abnormality.
‑ Module fault results in failure of external serial communication for matched MFP processor.
Thermal‑power plant, chemical‑plant legacy control system; ABB Bailey INFI‑90 / Symphony‑Harmony DCS; industrial spare‑part for MFP processor serial‑interface termination unit.
- INFI‑90 DCS dedicated NIMP01 multi‑function processor termination module, provides isolated RS‑232‑C / configurable RS‑485 serial physical interface for MFP multi‑function processor.
- Hardware jumper configurable serial mode, adapts to point‑to‑point and multi‑drop bus communication scenarios.
- Serial‑port galvanic‑isolation design, improves anti‑interference performance for field serial communication.
- Standard PCU rack plug‑in structure, convenient cabinet installation and spare‑part replacement.
- Legacy discontinued DCS component, mainly applied in old‑system maintenance and retrofit projects.