ABB NSSM01 Superloop Storage Module

The NSSM01 is a plug‑in Superloop storage module for ABB Bailey INFI‑90 / Network 90 legacy DCS system. It maintains the Superloop network communication table, interprets bus data stream, stores network configuration and node mapping information for the Superloop control loop. It cooperates with INICT01 computer transfer module to realize stable data exchange between Superloop network and external host computer. This is discontinued legacy DCS hardware, mainly used for spare‑parts replacement of old power plant and chemical‑plant control systems. Not hot‑swappable.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware Electrical Specifications

‑ Power Supply:Supplied by PCU rack back‑plane, typical power consumption 7.0 W

‑ Mechanical Structure:standard INFI‑90 PCU slot plug‑in module, front‑panel locking handle;weight approx 0.83 kg

‑ On‑board Resources:Superloop bus interface unit, configuration data memory, network table processing logic, module self‑diagnosis circuit

‑ Communication Interface:Superloop high‑speed control loop interface, internal PCU back‑plane bus

‑ Galvanic Isolation:galvanic isolation between Superloop network side and internal logic side, isolation rating 2500 VAC

‑ Core Function:Superloop network communication table maintenance, node address mapping, network data parsing, configuration parameter storage

‑ Protection:bus surge‑suppression protection

‑ Status LED Indicators:Power indicator, Module Fault indicator, Superloop network communication status LED

‑ Weight:approx 0.83 kg

Main Functions

‑ Stores Superloop network configuration table and each node address mapping data, supports normal operation of Superloop high‑speed control loop.

‑ Parses Superloop bus data stream, completes data buffering and forwarding, cooperates with INICT01 module to finish data interaction between DCS network and external host computer.

‑ Real‑time monitors Superloop loop operating status, detects network communication abnormality and node fault.

‑ Module self‑diagnosis monitors back‑plane power supply, memory health and Superloop link status; detects hardware failure and reports fault status to DCS system.

‑ Cannot run independently; must be installed in INFI‑90 PCU rack and cooperate with INICT01 computer transfer module. NSSM01 belongs to legacy DCS hardware, only compatible with INFI‑90 / Network90 system.

Control & Monitoring Function

‑ Continuously monitors back‑plane power supply, memory integrity, Superloop link and module hardware health. Detected faults activate fault LED and report fault word to DCS controller.

‑ No local historical‑data storage; module status and fault codes are read through DCS system or commissioning tool.

‑ Module hardware failure will cause Superloop network table loss; communication channel between Superloop loop and external computer fails, partial network node communication abnormality occurs.

Communication Interfaces

‑ Back‑plane connector: inserts into INFI‑90 PCU rack slot, connects to rack internal bus.

‑ Superloop interface: connects to Superloop control loop communication cable.

Environmental Specifications

‑ Mounting:insert into standard INFI‑90 PCU card rack slot

‑ Operating Temperature:‑10 ℃ ~ +60 ℃

‑ Storage Temperature:‑40 ℃ ~ +70 ℃

‑ Relative Humidity:5‑95 %RH, non‑condensing

‑ Protection Class:IP20, cabinet‑internal installation.

System Complementary Components
  1. NSSM01 Superloop storage module
Complementary parts: INFI‑90 PCU card rack, INICT01 computer transfer module, Superloop communication cable, DCS configuration software.
Installation Notes

‑ Power off PCU rack before inserting or removing this module. After replacement, download Superloop network configuration parameters, otherwise network table will be lost.

‑ For spare‑part replacement: verify model NSSM01; after installation check back‑plane power supply, verify Superloop network status and INICT01 communication function. Hardware version mismatch will lead to network‑table parsing error.

‑ Module fault results in Superloop network configuration loss and computer‑DCS communication channel failure.

Typical Application Scenarios

Thermal‑power plant, chemical‑plant legacy control system; ABB Bailey INFI‑90 / Network90 DCS; industrial spare‑part for Superloop network data‑processing unit.

Key Features
  1. INFI‑90 DCS dedicated NSSM01 Superloop storage module, undertakes Superloop network communication‑table maintenance, node mapping and network‑data parsing function, hardware variant NSSM01.
  2. Standard PCU rack plug‑in structure, convenient for cabinet installation and spare‑part replacement.
  3. Stores network configuration parameters, guarantees Superloop high‑speed control‑loop stable operation.
  4. Cooperates with INICT01 module to realize host‑computer data interaction.
  5. Legacy discontinued DCS component, mainly applied for old‑system maintenance and retrofit projects.