ABB PP835 3BSE042234R1 Panel 800 6.5‑inch Color Touch Operator Panel

The PP835 belongs to ABB Panel 800 series human‑machine‑interface hardware, specially developed for ABB System 800xA DCS platform. It is a cabinet flush‑mount industrial touch‑screen operator panel for process monitoring, parameter adjustment, alarm review and event handling. It communicates with AC 800M controllers via industrial Ethernet. HMI application projects are configured with ABB Panel Builder 800 engineering software. This unit only provides human‑machine‑interface visualization and operation functions and cannot execute independent process‑control logic. Widely deployed in power plants, pulp‑and‑paper mills, chemical plants and other process‑industry sites as local operator stations.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware and Performance Specifications

Display: 6.5‑inch TFT‑LCD color screen, resolution 640 × 480 pixels (VGA), 64 k colors, CCFL backlight.

Operation: 4‑wire analog resistive touch screen, touch lifetime ≥ 1 million operations.

Processor: 400 MHz RISC processor.

Memory: 128 MB flash memory, 64 MB SDRAM; battery‑backed real‑time clock and recipe‑data storage area.

Power supply: 24 V DC (18‑32 V DC), reverse‑polarity protection, maximum power consumption 10 VA.

Communication interfaces: 1×10/100 Mbps RJ45 Ethernet port, dual serial ports (RS232, RS422/485), 1×USB 2.0 host port.

Protection rating: Front panel IP66 (valid with correct gasket and cabinet installation), rear side IP20.

Operating temperature: −10 ℃ ~ +55 ℃; storage temperature: −40 ℃ ~ +70 ℃; humidity 10‑90 %RH non‑condensing.

Mechanical data: Die‑cast powder‑coated aluminum housing; cabinet cut‑out dimension 204 mm × 143 mm; net weight approx 1.4 kg; certifications: CE, UL/cULus.

Main Functions

Real‑time process graphic visualization, numeric value, bar‑chart and status‑indicator display. Multi‑level user password access management, alarm and event logging, historical trend curve display, recipe storage and download. Multi‑language text support and offline simulation function are available within Panel Builder 800 software. Optimized for native System 800xA object‑oriented communication.

Difference compared with PP826: PP835 is 6.5‑inch intermediate‑size Panel 800 HMI; PP826 adopts 8.4‑inch larger display. Both belong to Panel 800 series for System 800xA DCS. PP835A (3BSE042234R2) is its revised successor version.
Installation Requirement

Cabinet flush‑mount installation. Confirm cabinet cut‑out dimension complies with mechanical drawing and fit front‑panel sealing gasket properly to guarantee IP66 front‑panel protection. Separate signal cables from high‑power cables to reduce electromagnetic interference. After panel replacement, download complete HMI application project, verify Ethernet communication with AC 800M controller and normal process‑data display. Periodically replace internal backup lithium battery to prevent RTC clock and recipe‑data loss.

Typical Application Scenarios

Power‑plant auxiliary control, pulp‑and‑paper mills, chemical plants and general process‑industry facilities, deployed as local operator panel for on‑site process monitoring and parameter adjustment under System 800xA DCS system.

Key Features
  1. ABB Panel 800‑series 6.5‑inch resistive‑touch operator panel for System 800xA DCS environment.
  2. Equipped with Ethernet, dual serial and USB interfaces for flexible device interconnection.
  3. Die‑cast aluminum housing, front‑panel IP66 protection, suitable for dusty and humid process‑industry environments.
  4. Supports alarm logging, historical trend curves, recipe management and multi‑level user‑access authority.
  5. Application project configured by Panel Builder 800 software; no standalone process‑control capability.
  6. Industrial spare‑part for maintenance and retrofitting of legacy ABB System 800xA installations.