Description
Hardware & Electrical Specifications
- Model:PU519
- Part Number:3BSE018681R1
- Module Type:Dual‑Channel Real‑Time Accelerator (RTA) PCI Board
- Bus Interface:32‑bit 33 MHz PCI, supports 5V PCI signaling
- On‑board Memory:16 MB RAM for real‑time data buffering
- Communication Ports:2×15‑pin D‑Sub female for MB300 bus; 1×USB port
- Max bus speed:10000 kbit/s for MB300
- Power supply:Supplied via PCI slot
- Max power consumption:13 W
- Galvanic isolation:≥2000 V AC between field bus side and PCI host side
- Dielectric strength:2000 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, transient surge suppression, hardware watchdog, conformal coated PCB
- Compatibility note: Can be replaced by PU515A (USB function lost); driver and firmware must strictly match Advant OCS software release; supports dual‑channel MB300 redundancy.
Environmental Specifications
- Operating temperature:0 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:Installed inside industrial workstation chassis
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Standard full‑length PCI long‑card, insert into 5V PCI slot of Advant workstation
- Interfaces:PCI gold‑finger edge connector; two 15‑pin D‑Sub female for MB300; 1×USB port
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:Standard full‑length PCI card
- Weight:approx 0.40 kg
Main Functions
- Real‑time task off‑loading: Off‑load time‑critical real‑time processing tasks from workstation host CPU, provide deterministic low‑latency processing for Advant OCS DCS system.
- Dual‑channel MB300 fieldbus redundant communication: Two independent MB300 bus channels, realize bidirectional high‑speed data exchange between workstation and field controllers, support communication redundancy to improve system reliability.
- Real‑time data buffering: On‑board 16 MB RAM buffers bus I/O data, alarm and event messages, avoid data loss under high‑load operating condition.
- Hardware‑accelerated MB300 protocol processing: Process MB300 bus protocol on board, reduce host CPU overhead.
- USB local maintenance interface: USB port supports local board‑level maintenance and diagnostic operation.
- Board‑level self‑diagnosis: Monitor PCI bus status, dual MB300 channel status, on‑board power and watchdog circuit; report hardware failure and communication fault to Advant OCS system.
- On‑board multi‑LED status indication
- Green LED:Board power supply normal, RTA core running healthy
- Yellow LED:MB300 channel communication active
- Red LED:Hardware fault / bus communication failure alarm
Installation & Wiring Requirements
- Power off industrial workstation completely before installation; insert PU519 into available 5V PCI slot, fasten bracket screw firmly. Hot‑swap is strictly forbidden.
- Connect MB300 bus cables to two 15‑pin D‑Sub connectors; follow MB300 bus wiring specification, install correct terminal resistor at bus end point.
- Workstation chassis protective grounding must comply with ABB Advant OCS system grounding specification to improve anti‑interference performance.
- After replacement, install matched RTA driver and firmware corresponding to Advant OCS software version; verify dual‑channel MB300 bus communication status and redundancy switching function.
- Replacement note: When replaced with PU515A, USB function will not be available; confirm whole‑system driver‑firmware matching.






-300x300.jpg)
Reviews
There are no reviews yet.