Description
CT secondary rated:1 A /5 A configurable
System frequency:50 Hz /60 Hz
Auxiliary supply:36‑312 V DC wide‑range DC power
Sampling rate:600 Hz @50 Hz system,720 Hz @60 Hz system
Analog input channels:expandable via plug‑in analog boards
Binary input / output:expandable by different binary I/O modules
Communication interfaces:SPA bus, LON bus, RS‑423 local service port
Fault recording:non‑volatile event log, disturbance waveform storage
Mounting mode:19‑inch standard rack‑mount modular rack chassis
Operating temperature:‑25 ℃ ~ +70 ℃
Storage temperature:‑40 ℃ ~ +85 ℃
Humidity:5‑95 %RH non‑condensing
EMC compliance:IEC 60255‑22‑1 /‑22‑2 /‑22‑3
Certifications:CE, UL, IEC 60255 approval
Generator differential protection, stator earth‑fault protection, rotor earth‑fault protection, loss‑of‑excitation protection, reverse‑power protection, directional / non‑directional overcurrent protection, over‑voltage / under‑voltage protection, over‑frequency / under‑frequency protection.
Support configurable protection setting groups, event sequence logging and disturbance recording.
Real‑time hardware self‑diagnosis for each plug‑in module, fault alarm output.
Support dual‑processor and dual‑power redundant configuration to meet high‑reliability generator protection requirements.
Parameter configuration and commissioning are completed by dedicated REG216 engineering software.
Installed in 19‑inch standard rack inside power‑plant protection cabinet. Strictly follow CT/VT polarity for analog wiring, prohibit CT secondary open‑circuit risk. Auxiliary power supply shall be within rated DC range. After module replacement, download complete project configuration, perform protection logic verification, binary input/output point‑to‑point test and communication test with upper monitoring system. Confirm no self‑diagnosis fault alarms of each plug‑in unit.
Main protection and backup protection for small‑and‑medium‑size generators and main transformers in thermal power plants, hydropower plants and industrial self‑power stations.
- Full modular rack‑based generator protection system, each functional unit can be replaced individually.
- Support dual‑processor and dual‑power‑supply redundancy for high‑reliability generator protection occasions.
- Complete generator‑specialized protection function library, covers stator, rotor and abnormal operating‑condition protection.
- Full‑digital high‑speed sampling processing, good performance under CT saturation condition.
- Non‑volatile large‑capacity event and disturbance recording memory.
- Discontinued legacy ABB spare‑part, for maintenance and retrofitting of existing generator protection systems.






-300x300.jpg)
Reviews
There are no reviews yet.