ABB REG670 Generator‑Transformer Protection and Control IED

The REG670 belongs to ABB Relion 670 series high‑performance generator‑transformer intelligent electronic device, used for main and backup protection, control, measurement and supervision of generators, generator‑transformer blocks and shunt reactors in thermal‑power, hydro‑power, pumped‑storage and nuclear power plants. It adopts withdrawable plug‑in chassis architecture; analog input modules, binary I/O modules and communication modules support individual replacement. It features high‑speed sampling algorithm, excellent anti‑CT‑saturation performance. Fully compliant with IEC 61850 Ed.2 including GOOSE, PRP/HSR redundancy and process‑bus sampled‑value, also supports IEC 60870‑5‑103/104, DNP3 and Modbus protocols, suitable for both conventional and digital substation secondary systemsABB Group.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware and Performance Specifications

CT secondary rated: 1 A / 5 A configurable

VT secondary rated: 100 V

System frequency: 50 Hz / 60 Hz

Auxiliary supply: 24‑250 V DC / 85‑265 V AC universal wide‑range power

Total power consumption: ≤30 W

Analog input channels: maximum 24 configurable channels

Binary input / output: expandable via plug‑in modules

Local HMI: Graphic LCD display, LED status indicators and operation push‑buttons

Communication interfaces: Dual 10/100 Mbps Ethernet ports, RS485 serial port; supports PRP/HSR network redundancy, IRIG‑B time synchronization

Fault recording: COMTRADE disturbance waveform storage, large‑capacity time‑stamped sequential‑of‑event log

Mounting mode: 19‑inch standard rack‑mount, withdrawable plug‑in unit

Operating temperature: −25 ℃ ~ +55 ℃

Storage temperature: −40 ℃ ~ +85 ℃

Humidity: 5‑95 %RH non‑condensing

EMC compliance: IEC 60255‑22‑1 /‑22‑2 /‑22‑3

Certifications: CE, UL, IEC 60255, IEC 61850 approval

Main Functions

Generator differential protection, restricted earth‑fault protection, 100 % stator earth‑fault protection, sensitive rotor earth‑fault protection, loss‑of‑excitation protection, out‑of‑step / pole‑slip protection, reverse‑power protection, over‑excitation protection.

Directional / non‑directional phase overcurrent & earth‑fault protection, negative‑sequence overcurrent protection, thermal overload protection, over‑voltage / under‑voltage protection, over‑frequency / under‑frequency protection.

Breaker failure protection, configurable auto‑reclosing and programmable logic functions.

Realize local & remote circuit‑breaker control and bay‑level interlock logic, trip‑circuit supervision.

High‑accuracy measurement for current, voltage, active/reactive power, energy and frequency.

Multiple setting‑group management, sequential‑of‑event logging and COMTRADE disturbance waveform recording.

Continuous hardware self‑diagnosis detects internal module faults and uploads alarm status to local HMI and station control system.

Configuration and commissioning are completed by PCM600 engineering toolManualsLib。

Installation Requirement

Installed in 19‑inch standard rack inside power‑plant protection cabinet. Strictly comply with CT/VT polarity for secondary wiring, prohibit CT secondary open‑circuit risk. Auxiliary power supply shall be kept within rated voltage range. After unit or module replacement, download complete project configuration file. Perform protection logic verification test, breaker trip‑close loop test, binary input/output point‑to‑point signal test and station‑control communication validation. Confirm no hardware self‑diagnosis fault alarms.

Typical Application Scenarios

Main and backup protection for large‑medium‑size generators, generator‑transformer blocks and shunt reactors in thermal power plants, hydropower plants, pumped‑storage power stations and nuclear power plants.

Key Features
  1. Relion 670 series high‑end dedicated generator‑transformer protection & control IED, withdrawable plug‑in mechanical structure for convenient on‑site module replacement and maintenance.
  2. Complete generator‑oriented protection function library, covers stator, rotor and various abnormal operating‑condition protection requirements.
  3. Excellent anti‑CT‑saturation performance for differential protection algorithm.
  4. Native IEC 61850 Ed.2, GOOSE, PRP/HSR network redundancy and process‑bus support, adapt to digital‑substation requirements.
  5. Integrated high‑accuracy measurement, time‑stamped event log and COMTRADE disturbance recording functions.
  6. Multiple communication protocol options, compatible with traditional and new‑generation substation automation systems.
  7. Industrial spare‑part for maintenance and retrofitting of ABB Relion 670‑series generator‑protection devices.