ABB RXEDK 2H 1MRK000841-KA Over‑ / Under‑Voltage Protection Relay

The RXEDK 2H 1MRK000841‑KA is a microprocessor‑based two‑stage over‑voltage and under‑voltage protection relay of ABB RX‑series protection assembliesABB У…. It provides two independent voltage‑measuring protection stages, each configurable for over‑voltage or under‑voltage function. Stage 1 supports both definite‑time and inverse‑time delay characteristics; Stage 2 adopts definite time‑delay. Optional filter modules can be equipped for third‑harmonic measurement for stator earth‑fault supervision. This is a legacy discontinued plug‑in type protection relay, widely preserved in existing power‑plant and substation secondary protection cabinets.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware and Performance Specifications

Rated measuring input: AC 20‑50 V

System frequency: 50 Hz / 60 Hz

Auxiliary supply: Wide‑range DC auxiliary power supply

Time‑delay setting range: 0.1‑10 s adjustable for each stage

Reset mode: Manual / automatic reset selectable

Output contacts: Multiple change‑over relay contacts for trip and alarm signals

Indicators: LED indicators for start, trip and operational status

Mounting: Plug‑in module for 19‑inch rack chassis

Operating temperature: −25 ℃ ~ +70 ℃

Storage temperature: −40 ℃ ~ +85 ℃

Humidity: 5‑95 %RH non‑condensing

EMC compliance: IEC 60255‑22‑1 /‑22‑2 /‑22‑3

Certifications: CE, IEC 60255 approval

Main Functions

Two‑stage independent over‑voltage / under‑voltage protection, freely assign function for each stage.

Stage 1: selectable definite‑time or inverse‑time delay characteristic.

Stage 2: definite‑time delay protection function.

Third‑harmonic‑based stator earth‑fault supervision (with optional filter accessory)ABB У….

Adjustable voltage threshold and time‑delay parameters for each protection stage.

Trip and alarm relay contact output, local LED status indication.

Continuous hardware self‑diagnosis for internal circuit fault detection.

Manual or automatic reset mode for protection operation.

Parameter setting completed by potentiometers and DIP switches on front panel.

Installation Requirement

Plug‑in installation inside 19‑inch standard protection rack. Strictly follow VT polarity for voltage‑circuit wiring, avoid voltage‑circuit short‑circuit risk. Auxiliary power supply shall keep within rated range. After module replacement, complete protection setting verification, operate‑condition simulation test for each stage, check trip‑alarm contact action. Confirm no self‑diagnosis fault indication.

Typical Application Scenarios

Generator stator earth‑fault supervision based on third‑harmonic voltage; over‑voltage / under‑voltage monitoring for generator and transformer auxiliary‑voltage circuits; neutral‑point voltage supervision in power plants and substationsABB У….

Key Features
  1. Two‑stage independent voltage‑protection design, flexible function assignment for over‑voltage / under‑voltage.
  2. Multiple time‑delay characteristic options, adaptive for different protection coordination requirements.
  3. Support third‑harmonic measuring function for generator stator earth‑fault monitoring with filter accessory.
  4. Plug‑in modular structure, convenient for on‑site replacement and maintenance.
  5. Local LED status indication, manual / automatic reset configurable.