Description
CT secondary rated: 1 A / 5 A configurable
System frequency: 50 Hz / 60 Hz
Auxiliary supply: Wide‑range DC auxiliary power supply
Current setting range: 0.5‑10 A adjustable
Time‑delay range: 0.1‑30 s adjustable for each stage
Reset mode: Manual / automatic reset selectable
Output contacts: Multiple change‑over relay contacts for trip and alarm outputs
Indicators: LED indicators for start, trip and power status
Mounting: Plug‑in module for 19‑inch standard protection rack
Operating temperature: −25 ℃ ~ +70 ℃
Storage temperature: −40 ℃ ~ +85 ℃
Humidity: 5‑95 %RH non‑condensing
EMC compliance: IEC 60255‑22‑1 /‑22‑2 /‑22‑3
Certifications: CE, IEC 60255 approval
Two‑stage independent over‑current protection.
Stage 1: selectable definite‑time or inverse‑time delay characteristic.
Stage 2: definite‑time delay over‑current protection.
Adjustable current threshold and time‑delay parameters for each protection stage.
Trip and alarm relay contact output, local LED operation status indication.
Continuous hardware self‑diagnosis for internal circuit fault detection.
Manual or automatic reset mode for protection operation.
Parameter setting completed by potentiometers and DIP switches on front panel.
Plug‑in installation inside 19‑inch standard protection rack. Strictly comply with CT polarity for secondary wiring, strictly prohibit CT secondary open‑circuit risk. Auxiliary power supply shall be kept within rated voltage range. After module replacement, complete protection setting verification, simulation test for each protection stage, check trip‑alarm contact action. Confirm no self‑diagnosis fault indication.
Over‑current backup protection for generators, transformers and transmission‑line bays in thermal‑power plants, hydropower plants and utility substations.
- Two‑stage independent over‑current protection design, flexible time‑characteristic selection for protection coordination.
- Potentiometer and DIP‑switch local setting, no special software required for commissioning.
- Plug‑in modular structure, convenient for on‑site replacement and maintenance.
- Local LED status indication, manual / automatic reset configurable.
- Discontinued legacy ABB spare‑part, used for maintenance and retrofitting of existing RX‑series protection assemblies.






-300x300.jpg)
Reviews
There are no reviews yet.