Description
Hardware & Electrical Specifications
- Model:UAC383AE01
- Part Number:HIEE300890R0001
- Module Type:Measurement Unit Board (MUB)
- Bus Interface:6U VME back‑plane bus for high‑speed data exchange with main processor
- Analog Input:Multi‑channel isolated analog input for generator voltage, current measurement
- Binary Input:Multi‑channel binary status input for cabinet auxiliary signal
- On‑board Resource:Signal conditioning circuit, A/D conversion unit, local logic circuit
- Power supply:24 V DC internal cabinet power supply
- Max power consumption:13 W
- Galvanic isolation:≥2500 V AC between field signal side and VME logic side
- Dielectric strength:2500 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:Surge suppression for input channels, ESD protection, over‑voltage protection, conformal coated PCB
- Compatibility note:Must match UNITROL6000 system firmware version; works together with PPC series processor boards; cannot be used standalone.
Environmental Specifications
- Operating temperature:‑10 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:Installed inside excitation cabinet VME rack
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Standard 6U VME Euro‑card, inserted into VME rack slot of excitation cabinet
- Interfaces:VME back‑plane gold‑finger connector; terminal block connectors for analog & binary signal input
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:6U VME standard board
- Weight:approx 0.72 kg
Main Functions
- Multi‑channel analog signal acquisition & conditioning: Collects generator voltage, current analog signals, completes filtering, isolation and signal conditioning before A/D conversion.
- High‑precision A/D conversion: Converts conditioned analog signals into digital measurement values, sends data to main processor board for excitation closed‑loop control calculation.
- Binary status signal input processing: Samples cabinet auxiliary binary signals, converts field contact status into digital data for system logic judgment and interlock protection.
- Real‑time measurement data transmission: Transmits measurement data and binary status to main processor via VME back‑plane bus.
- Input‑channel fault detection: Monitors analog input signal amplitude, detects signal loss, over‑range and channel abnormal condition, reports fault codes to main processor.
- Board‑level self‑diagnosis: Monitors on‑board power supply, A/D unit and hardware logic running status; uploads hardware fault information to UNITROL6000 system.
- On‑board multi‑LED status indication
- Green LED:Board power supply normal, board logic running healthy
- Yellow LED:Signal acquisition active, data transmission ongoing
- Red LED:Input‑channel fault / board hardware fault alarm
Installation & Wiring Requirements
- Cut off cabinet total power before disassembly and assembly. Insert UAC383AE01 into designated VME rack slot, lock front‑panel handles firmly. Hot‑swap is strictly forbidden.
- Connect generator measurement analog cables and cabinet binary‑signal cables to corresponding terminal blocks; strictly follow excitation cabinet wiring specification; separate high‑power cables and weak‑signal cables to reduce electromagnetic interference.
- Cabinet protective grounding must comply with ABB AC800‑PEC / UNITROL6000 system grounding specification.
- After replacement, verify full‑system firmware compatibility with main processor board; download matched project parameters; perform analog‑channel calibration and binary‑input function test before unit commissioning.
- Replacement note: Cannot operate independently; must cooperate with PPC series main‑processor hardware and matched full‑system firmware version.