ABB UFC718AE01 HIEE300936R0001 Communication Interface Board

UFC718AE01 (HIEE300936R0001) is a VME‑bus high‑performance communication interface board under ABB AC800‑PEC platform, applied for UNITROL6000 / UNITROL6000 X‑power static excitation systems. It connects to PPC902 / PPC905 / PPC907BE main processor via VME back‑plane bus. It implements multi‑protocol external communication data processing, undertakes data interaction between excitation main controller and DCS, SCADA, remote HMI and third‑party automation equipment. It supports serial, Ethernet communication channels, completes protocol encapsulation, data parsing and communication status monitoring, realizes uploading of excitation measurement values, alarm events, fault records and downloading of control set‑points and parameters. Product status: Obsolete, spare‑part only supply available.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

  • Model:UFC718AE01
  • Part Number:HIEE300936R0001
  • Module Type:Communication Interface Board
  • Bus Interface:6U VME back‑plane bus for high‑speed data exchange with main processor
  • External Interface:Multi‑channel communication ports including Ethernet and serial interface
  • Supported Protocol:Modbus‑TCP, Modbus‑RTU and other automation communication protocols
  • Power supply:24 V DC cabinet internal power supply
  • Max power consumption:11 W
  • Galvanic isolation:≥2000 V AC between external communication side and VME control‑logic side
  • Dielectric strength:2000 V AC 1 minute
  • Insulation resistance:>100 MΩ @ 500 V DC
  • On‑board protection:ESD protection, surge suppression for communication ports, communication watchdog, conformal coated PCB
  • Compatibility note:Must match UNITROL6000 full‑system firmware; cannot operate standalone, must cooperate with PPC‑series main‑processor hardware.

Environmental Specifications

  • Operating temperature:‑10 ℃ ~ +60 ℃
  • Storage temperature:‑40 ℃ ~ +85 ℃
  • Relative humidity:5%‑95% non‑condensing
  • Protection degree:Installed inside excitation cabinet VME rack
  • EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
  • Certifications:CE

Mechanical Data

  • Installation:Standard 6U VME Euro‑card, inserted into VME rack slot of UNITROL6000 cabinet
  • Interfaces:VME back‑plane gold‑finger connector; external communication ports for field wiring
  • Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
  • Terminal tightening torque:0.6‑1.0 N·m
  • Weight:approx 0.70 kg
  • Dimension:6U VME standard board dimension

Main Functions

  1. Multi‑protocol communication processing: Executes Modbus‑TCP / Modbus‑RTU protocol stack, realizes bidirectional data interaction between excitation system and external automation system.
  2. Process‑data upload: Transmits generator voltage, current, excitation current, system status, alarm and fault event data from main processor to upper‑level DCS/SCADA system.
  3. Remote command receiving & parsing: Receives remote set‑point commands, parameter modification commands and control instructions from upper system, forwards valid commands to main processor.
  4. Communication link diagnosis: Detects communication link interruption, frame error and abnormal slave‑station response, reports communication fault codes to main processor.
  5. Real‑time data forwarding: Implements high‑speed data transmission between VME back‑plane bus and external communication physical ports.
  6. Board‑level self‑diagnosis: Monitors on‑board power supply, communication chip and VME link status; uploads hardware‑fault alarm information to UNITROL6000 system.
  7. On‑board multi‑LED status indication
    • Green LED:Board power supply normal, board logic running healthy
    • Yellow LED:External communication port data transmission active
    • Red LED:Communication‑link fault / board hardware fault alarm

Installation & Wiring Requirements

  1. Cut off cabinet total power before disassembly and assembly. Insert UFC718AE01 into designated VME rack slot and lock front‑panel handles firmly. Hot‑swap is strictly forbidden.
  2. Connect Ethernet cable and serial communication shielded cables to corresponding ports; strictly follow communication wiring specification, complete shielding grounding processing for communication cables to restrain electromagnetic interference.
  3. Cabinet protective grounding must comply with ABB AC800‑PEC / UNITROL6000 system grounding specification.
  4. After replacement, verify full‑system firmware compatibility with main processor board; download matching communication configuration parameters; perform communication link test and data point verification before unit commissioning.
  5. Replacement note: Cannot run independently; must match corresponding main‑processor hardware and full‑system firmware version.