Description
Hardware & Electrical Specifications
- Model:UFC765AE102
- Part Number:3BHE003604R0102
- Module Type:Drive & Protection Signal Interface Board
- Bus Interface:Internal high‑speed back‑plane connector for main‑processor data exchange
- Signal Channels:Multi‑channel auxiliary status input, earth‑fault detection input, temperature measuring input, interlock permission output channels
- Power supply:24 V DC cabinet internal power supply (18‑32 V DC)
- Max power consumption:13 W
- Galvanic isolation:≥2500 V AC between field‑signal side and control‑logic side
- Dielectric strength:2500 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, signal‑circuit surge suppression, earth‑fault detection circuit, hardware watchdog, conformal coated PCB
- Compatibility note:Must match UNITROL6000 full‑system firmware; cannot operate standalone, must cooperate with PPC‑series main‑processor hardware.
Environmental Specifications
- Operating temperature:‑10 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:Installed inside excitation / converter cabinet rack
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Plug‑in rack‑mount board, inserted into designated slot of UNITROL6000 / PCS6000 cabinet
- Interfaces:Internal back‑plane bus connector; external terminal blocks for auxiliary‑signal wiring
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Weight:approx 0.88 kg
- Dimension:Standard Euro‑card form‑factor for AC800‑PEC rack
Main Functions
- Auxiliary‑status signal acquisition: Collects working‑status feedback signals from thyristor power unit, cooling system and cabinet auxiliary equipment, completes signal conditioning and filtering.
- Earth‑fault monitoring: Realizes hardware‑level earth‑fault detection for power section, detects insulation abnormal of power valve loop, sends fault alarm to main processor.
- Temperature‑signal processing: Samples temperature signals from power‑unit temperature sensors, transmits temperature data for over‑temperature protection logic judgment.
- Interlock‑condition logic processing: Processes safety interlock signals, outputs permission‑related signals for power‑unit enabling, participates in hardware interlock protection chain.
- Fault‑signal reporting: Detects signal‑line breakage, signal deviation and channel abnormality, reports detailed fault codes to main controller.
- Board‑level comprehensive self‑diagnosis: Monitors on‑board power‑supply, signal‑processing circuit and back‑plane link status; uploads hardware‑fault‑alarm information to UNITROL6000 system.
- On‑board multi‑LED status indication
- Green LED:Board power supply normal, board logic running healthy
- Yellow LED:Auxiliary‑signal acquisition & data transmission active
- Red LED:Earth‑fault / over‑temperature / board hardware fault alarm
Installation & Wiring Requirements
- Cut off cabinet total power before disassembly and assembly. Insert UFC765AE102 into designated rack slot and fasten fixing screws firmly. Hot‑swap is strictly forbidden.
- Connect power‑unit auxiliary feedback, earth‑fault detection and temperature‑sensor cables strictly according to drawing; separate high‑power cables and weak‑signal cables to reduce electromagnetic interference.
- Cabinet protective grounding must comply with ABB AC800‑PEC / UNITROL6000 system grounding specification.
- After replacement, verify full‑system firmware compatibility with main processor board; download matching project parameters; perform signal‑channel test and interlock‑logic verification before unit commissioning.
- Replacement note: Cannot run independently; must match corresponding main‑processor hardware and full‑system firmware version.






Reviews