Description
Hardware & Electrical Specifications
- Model:UFC911B106
- Part Number:3BHE037864R0106
- Module Type:High‑Speed Serial Communication Interface Board
- Bus Interface:Internal high‑speed back‑plane connector for main‑processor interaction
- External Interface:High‑speed serial optical / electrical communication ports
- Power supply:24 V DC (18‑32 V DC)
- Max power consumption:11 W
- Galvanic isolation:≥2000 V AC between external communication side and control‑logic side
- Dielectric strength:2000 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, port surge suppression, communication watchdog, hardware link‑loss detection, conformal coated PCB
- Compatibility note:Cannot run standalone; must match UNITROL6000 system firmware and PPC‑series main‑processor hardware. Cross‑model replacement with UFC911B101 / B104 needs full hardware‑firmware compatibility validation.
Environmental Specifications
- Operating temperature:‑10 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Inside excitation / converter cabinet rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Installation:Plug‑in rack‑mount board
- Interfaces:Internal back‑plane bus connector; front‑panel high‑speed serial communication ports
- Recommended wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Weight:approx 0.74 kg
- Dimension:Standard Euro‑card for AC800‑PEC rack
Main Functions
- Dedicated high‑speed serial communication processing, real‑time bidirectional data exchange between main controller and other functional units.
- Transmit trigger timing‑sequence data, analog sampling data, safety interlock status and fault information between boards.
- Communication link fault diagnosis: detect link break, frame error, signal loss and transmission abnormality, report fault codes to main CPU.
- Hardware data buffer, guarantee real‑time performance for power‑electronic control loop.
- Complete board self‑diagnosis for power supply, communication chip and back‑plane link; upload hardware alarm to UNITROL6000 system.
- LED status indication:
- Green LED:Power supply normal, board logic healthy
- Yellow LED:Serial communication active, data transferring
- Red LED:Communication link fault / board hardware fault
Installation & Wiring Requirements
- Cut off cabinet total power before installation or replacement. Insert UFC911B106 into assigned rack slot and tighten mounting screws. Hot‑swap is strictly forbidden.
- Connect high‑speed serial cables or optical fibers to front‑panel ports; properly ground shield layer of electrical cables to reduce electromagnetic interference.
- Cabinet protective grounding shall follow ABB AC800‑PEC / UNITROL6000 grounding specification.
- After replacement, confirm firmware compatibility with main processor, download project parameters, perform communication link test and signal verification before commissioning.
- Replacement note: Verify hardware variant compatibility before cross‑revision substitution.





Reviews