Description
Hardware & Electrical Specifications
- Model:XVC770BE101
- Part Number:3BHE021083R0101
- Module Type:DC‑Link High‑Voltage Detection HVD Board
- Bus Interface:Internal converter system back‑plane signal bus
- Signal Channel:DC‑link high‑voltage sampling input, analog measuring output, hardware fault trigger output
- Power supply:24 V DC (18‑32 V DC)
- Max power consumption:10 W
- Galvanic isolation:≥3000 V AC between high‑voltage sampling side and control‑logic side
- Dielectric strength:3000 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, high‑voltage surge suppression, hardware voltage comparator latch circuit, conformal coated PCB
- Compatibility note:Cannot run standalone; dedicated for ACS6000 / Megadrive‑LCI converter rack, must match corresponding system firmware version. Direct swap with XVC770AE needs hardware‑firmware compatibility validation.
Environmental Specifications
- Operating temperature:‑10 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Inside high‑power converter cabinet rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Installation:Plug‑in rack‑mount eurocard board
- Interfaces:Internal back‑plane connector; high‑voltage sampling terminals; fault‑signal output terminal blocks
- Recommended wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Weight:approx 0.78 kg
- Dimension:Standard Euro‑card for ABB high‑power converter rack
Main Functions
- Real‑time sampling and galvanic isolation conversion of converter DC‑link high‑voltage signal.
- Hardware‑level fast over‑voltage / under‑voltage detection, independent of main‑processor software logic.
- Output hardware fault trigger signal to control system to execute trip sequence once voltage threshold exceeded.
- Send scaled analog measuring data to main processor for closed‑loop control and high‑voltage monitoring.
- Board‑level self‑diagnosis: detect sampling‑circuit abnormality and board power‑supply failure, report fault codes to converter system.
- LED status indication:
- Green LED:Power supply normal, board logic healthy
- Yellow LED:High‑voltage sampling signal active
- Red LED:Over‑voltage / under‑voltage fault / sampling channel fault / board hardware fault
Installation & Wiring Requirements
- Cut off cabinet total power before replacement. Insert XVC770BE101 into assigned rack slot and tighten mounting screws. Hot‑swap is strictly forbidden.
- Connect DC‑link sampling cables and fault‑signal cables strictly per wiring drawing; strictly separate high‑voltage sampling cables and low‑voltage signal cables to reduce electromagnetic interference.
- Cabinet protective grounding shall comply with ABB ACS6000 / Megadrive‑LCI grounding specification.
- After replacement, confirm firmware compatibility, complete high‑voltage sampling calibration and over‑voltage protection simulation test before commissioning.
- Replacement note:Cross‑version substitution requires hardware‑firmware compatibility confirmation.