Description
Hardware & Electrical Specifications
- Model:XXD129A01
- Part Number:3BHE012436R0001
- Module Type:PEC800‑BP Back‑Plane Interface Board
- Bus Interface:AC800‑PEC high‑speed internal back‑plane bus
- Signal Channel:Multi‑slot module signal routing, system power distribution channels
- Power supply:24 V DC (18‑32 V DC), power fed from rack power unit
- Max power consumption:8 W
- Galvanic isolation:≥2000 V AC between field signal side and control logic side
- Dielectric strength:2000 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, bus signal surge suppression, filter circuit, conformal coated PCB
- Compatibility note:Cannot run standalone; dedicated for AC800‑PEC rack, must match corresponding system firmware version.
Environmental Specifications
- Operating temperature:‑10 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Inside excitation / converter cabinet rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Installation:Plug‑in rack‑mount eurocard board
- Interfaces:Multi‑channel internal back‑plane slot connectors; auxiliary signal terminal blocks
- Recommended wire cross‑section:0.75 mm²‑2.5 mm² copper cable for auxiliary signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Weight:approx 0.65 kg
- Dimension:Standard Euro‑card for ABB AC800‑PEC rack
Main Functions
- Physical and electrical interconnection for each plug‑in module inside AC800‑PEC rack.
- Distribute 24 V system power supply to each functional board.
- Route high‑speed back‑plane address, data and control signals between CPU and peripheral boards.
- Signal filtering and impedance matching, restrain electromagnetic interference inside cabinet.
- Bus‑level self‑diagnosis: detect bus communication abnormality and power‑supply distribution fault, report fault codes to main processor.
- LED status indication:
- Green LED:Power supply normal, back‑plane bus logic healthy
- Yellow LED:Back‑plane bus communication active
- Red LED:Bus communication fault / power distribution fault / board hardware fault
Installation & Wiring Requirements
- Cut off cabinet total power before replacement. Insert XXD129A01 into assigned rack slot and tighten mounting screws. Hot‑swap is strictly forbidden.
- Ensure each daughter board is fully seated into back‑plane connector; separate high‑power cables and weak‑signal cables to reduce electromagnetic interference.
- Cabinet protective grounding shall comply with ABB AC800‑PEC / UNITROL6000 grounding specification.
- After replacement, confirm firmware compatibility, complete rack bus communication test before commissioning.
- Replacement note:Cross‑version substitution requires hardware‑firmware compatibility validation.


-300x300.jpg)



Reviews