Description
Hardware & Electrical Specifications
‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500 machinery protection system, 3500/15 universal AC power subsystem ‑ Functional Type: Universal AC Power Input Module (PIM, half‑height small card) ‑ Mandatory Mating Unit: 106M1079‑01 (universal AC power supply main card) ‑ AC Input Range: 85‑264 VAC, frequency 47‑63 Hz ‑ Max Power Capacity: 120 W full rack power supply capability ‑ Protection: Input over‑current, surge, over‑voltage and reverse‑transient protection ‑ Indicators: Front‑panel OK status LED for power‑input health diagnosis ‑ Connectors: Screw‑terminal block for AC mains input; internal edge‑card connector mates with 106M1079‑01 main power card ‑ Mounting: Half‑height slot installation on the left dedicated position of 3500 rack ‑ PCB Finish: Conformal coated for ISA‑S71.04 G3 harsh power‑plant cabinet environment ‑ Hot‑swap: Hot‑swappable only under redundant dual‑power configuration. Cut off AC source for single‑supply rack before replacement
Environmental Specifications
‑ Operating Temperature: ‑40 °C ~ +70 °C, power derating at high ambient temperature ‑ Storage Temperature: ‑40 °C ~ +85 °C ‑ Relative Humidity: 5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 and power‑industry cabinet EMC transient requirements
Mechanical Data
‑ Weight: approx 0.34 kgNEX Instru… ‑ Form‑factor: Half‑height small‑card for 3500 rack
Core Functions
- AC power front‑end gateway: Accepts site wide‑range AC mains input, performs filtering and surge protection, delivers conditioned AC power to 106M1079‑01 power supply main card.
- Redundancy support: Supports dual‑PIM+dual‑PSU N+1 redundant power architecture to improve 3500 rack system availability.
- Input‑side fault protection: Isolates AC‑side surge and over‑current faults, avoids damaging downstream power‑conversion main card and other monitoring modules.
- Visual health diagnosis: OK LED quickly indicates AC input power and PIM module operational status for field maintenance.
- Rack power subsystem cooperation: Works with 106M1079‑01 to generate ±5 V, ±15 V, 24 VDC multi‑rail power for all vibration‑monitoring and protection cards inside 3500 rack.
Installation, Replacement & Critical Warnings
- For non‑redundant single‑power rack, fully de‑energize upstream AC input before replacement. Hot‑swap is only allowed when redundant power is configured.
- Must pair with matching 106M1079‑01 universal AC power main card; legacy HV‑AC / LV‑AC power units are incompatible with this PIM, cannot be mixed‑used.
- Torque AC input screw terminals to specified torque value; loose terminals produce overheating and intermittent rack power drop‑out.
- After installation, check OK LED status, verify 3500 rack boots normally, complete module configuration download via 3500 Rack Configuration software.
-
Common failure mode: AC‑side electrical surge damage to input circuit. Investigate site AC power quality and check upstream fuse when PIM OK LED goes off and whole rack loses power.


-300x300.jpg)



Reviews