Bently 125840-02 15小卡 Low‑Voltage AC Power Input Module (PIM) for 3500/15 Power Supply

The 125840‑02 is the rear‑slot power input small card (PIM‑Power Input Module) matched with the 3500/15 low‑voltage AC power supply, mounted in the dedicated rear power slot of the 3500 rack. It accepts low‑voltage 85‑132 Vac mains input, provides screw‑type terminals for AC field wiring, and transfers AC input power to the front‑side 3500/15 power converter via rack backplane. It integrates surge suppression, EMI filtering and internal fuse protection circuits. This unit supports dual redundant power configuration for the 3500 monitoring rack. Hot‑swap operation is not allowed. Mismatched input voltage or poor terminal contact will lead to power‑supply shutdown and complete loss of rack measurement and protection functions.

Email:2306444920@qq.com
Phone:+86 17759635229

Description

Hardware & Electrical Specifications

‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Device Type: Low‑Voltage AC Power Input Module (PIM) for 3500/15 ‑ Input Voltage Range: 85‑132 Vac RMS ‑ Input Frequency: 47‑63 Hz ‑ Maximum Input Current: 4 A ‑ Termination: Screw‑type terminal blocks for field AC power wiring ‑ Built‑in Protection: Internal fuse, surge absorber, EMI input filter ‑ Backplane Interface: 3500 proprietary backplane mating with front‑side 3500/15 low‑voltage AC power module ‑ Mounting: Full‑height dedicated rear power slot inside 3500‑series rack chassis ‑ PCB Treatment: Conformal‑coated printed‑circuit board ‑ Operating Temperature: ‑30 ℃ ~ +65 ℃ ‑ Storage Temperature: ‑40 ℃ ~ +85 ℃ ‑ Certifications: CE, CSA, ATEX hazardous‑area approvals, API‑670 compliant

Environmental Specifications

‑ Relative Humidity: 5%‑95 %, non‑condensing ‑ Vibration Resistance: Complies with industrial cabinet mechanical vibration requirements ‑ EMI Immunity: On‑board filtering suppresses power‑line surge and conducted noise interference

Core Functions

  1. Low‑voltage AC mains termination: Provides screw terminals for 85‑132 Vac field power input wiring for the paired 3500/15 power supply.
  2. Input power conditioning: Integrates surge‑suppression and EMI‑filter circuits to attenuate power‑line spikes and noise before delivering power to front‑side 3500/15 converter.
  3. Over‑current fuse protection: Internal fuse cuts off input circuit under over‑current fault to prevent secondary damage to rack power hardware.
  4. Redundant power support: Two sets of 3500/15 plus 125840‑02 can be configured for dual‑redundant rack power, achieving automatic power switching upon single‑path power failure.
  5. Power‑path transmission: Transfers conditioned low‑voltage AC input through backplane bus to front‑side 3500/15 module for DC conversion to rack internal power rails.

Installation, Replacement & Critical Warnings

  1. This power‑input module is non‑hot‑swappable. Disconnect field high‑voltage AC input power completely before inserting or removing the module.
  2. Compatibility warning: ‑ Strictly matched with front‑side 3500/15 low‑voltage AC power supply; cannot pair with high‑voltage AC or DC‑type 3500/15 variants. ‑ Input terminals carry hazardous AC voltage; strictly follow high‑voltage safety operating procedures. ‑ Torque AC power terminals to specified torque value to prevent over‑heating caused by loose connections. ‑ Inspect backplane connector pins for bending, debris and corrosion before module insertion. ‑ When configuring dual‑redundant power, two independent AC power sources are recommended for true redundancy.
  3. Post‑replacement commissioning and verification: ‑ Confirm module is fully seated in rear dedicated power slot with reliable backplane connection. ‑ Apply rated 85‑132 Vac input voltage; verify front‑side 3500/15 “Power OK” indicator illuminates normally. ‑ Confirm all rack monitor modules power‑up without hardware‑fault alarms. ‑ Simulate single‑power loss under redundant configuration, verify rack keeps normal operation without measurement interruption.

Common Failure Modes and Symptoms

‑ Internal fuse blown: No power delivery to front‑side 3500/15, full‑rack power loss. ‑ Terminal loose / over‑heating: Intermittent rack power drop‑out, sporadic rack reset events. ‑ Surge‑component damage: Power‑supply shutdown upon power‑line surge events. ‑ Backplane contact degradation: Intermittent power transfer, flickering power‑ok status. ‑ Mismatched front‑side power module: Front‑side 3500/15 reports power‑input fault, rack cannot start‑up.

Reviews

There are no reviews yet.

Be the first to review “Bently 125840-02 15小卡 Low‑Voltage AC Power Input Module (PIM) for 3500/15 Power Supply”

Your email address will not be published. Required fields are marked *