Description
Hardware & Electrical Specifications
‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 1900 series machinery monitoring platform ‑ Functional Type: Multi‑Purpose Machinery Monitor(with Modbus‑TCP Ethernet) ‑ Input Channels: • 4 configurable dynamic transducer inputs (eddy‑current probe, ICP accelerometer, velocity sensor, tachometer pulse) • 4 temperature inputs: 2‑/3‑wire RTD, Type E/J/K/T thermocouples ‑ Communication Interfaces: RJ45 Ethernet(Modbus‑TCP)+ RS485 Modbus‑RTU ‑ Analog Output: 4 isolated 4‑20 mA outputs, freely assignable to measurement variables ‑ Relay Output: 6 × SPDT programmable relay contacts for Alert, Danger, module fault ‑ Diagnostics: Transducer open‑circuit / short‑circuit detection; BNC buffered waveform output per channel ‑ Event Storage: 200‑entry timestamp fault event log ‑ Auxiliary Power: 18‑36 VDC wide‑range DC supply ‑ Indicators: Multi‑LED for power, module fault, channel alarm status ‑ Connectors: Removable screw terminal blocks for power, I/O; RJ45 Ethernet; BNC test ports ‑ Mounting: 35 mm DIN‑rail installation ‑ Enclosure: Metal housing, IP20 ‑ Certification: Standard CE, no hazardous‑location approval ‑ Hot‑swap: Non‑hot‑swappable; de‑energize DC power before replacement
Environmental Specifications
‑ Operating Temperature: ‑20 °C ~ +60 °C ‑ Storage Temperature: ‑40 °C ~ +85 °C ‑ Relative Humidity: 5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 industrial cabinet EMC standards
Mechanical Data
‑ Weight: approx 1.1 kg
Core Functions
- Multi‑parameter signal acquisition: Collect shaft vibration, thrust displacement, housing vibration, rotating speed and bearing‑temperature signals for auxiliary rotating‑machinery condition monitoring.
- Two‑level alarm supervision: Configurable Alert / Danger thresholds with adjustable time‑delay; latching / non‑latching relay mode selectable to suppress startup nuisance alarms.
- Multiple output interfaces: 4‑20 mA analog outputs send trending data to DCS/PLC; relay contacts output alarm signals to local annunciator.
- Dual‑mode digital communication: Modbus‑TCP over Ethernet + Modbus‑RTU over RS485, upload real‑time data and fault logs to plant SCADA / System 1 software.
- On‑site troubleshooting: BNC buffered ports output raw transducer waveform for oscilloscope inspection; historical fault records support post‑incident analysis.
Installation, Replacement & Critical Warnings
- De‑energize 18‑36 VDC auxiliary power before replacement; unit is non‑hot‑swappable. Isolate field sensor wiring for terminal maintenance.
- This suffix variant has built‑in Ethernet Modbus‑TCP; cannot be directly replaced by the no‑Ethernet 01‑suffix version, otherwise Ethernet communication function will be lost.
- After hardware replacement, download site‑specific configuration via 1900 configuration software; factory default parameters cannot be used for field operation.
- After power‑on, verify LED status, channel reading, 4‑20 mA loop, relay‑alarm action and Modbus‑TCP data communication.
-
Common failure mode: Ethernet transceiver surge damage, field‑wiring damage to transducer input circuits. Inspect sensor cables and grounding when transducer‑fault alarms trigger.