Description
Hardware & Electrical Specifications
‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI machinery‑protection rack, matches M‑series monitor cards ‑ Functional Type: M‑series Up‑graded 4‑Channel Relay Module ‑ Channel quantity: 4 isolated SPDT (Form‑C) relay channels ‑ Relay Contact Rating: AC: 2A @250 VAC, max 450 VA DC: 2A @30 VDC; 0.75A @48 VDC; 0.2A @125 VDC Minimum switched current:100 mA @12 VDC ‑ Typical power consumption: 5.8 W, powered by rack backplane busBaker Hugh… ‑ Front‑panel Indicators: OK LED, TX/RX LED, four channel alarm status LED ‑ Matching Parts: Main‑board 149986‑02 must pair with rear I/O board 125720‑02, sold separately ‑ Hot‑swap: Supports hot‑swap. During replacement, measurement channels keep running; corresponding relay output is temporarily invalid. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2, ATEX / IECEx, cNRTLus hazardous area approval option available
Environmental Specifications
‑ Operating Temperature:‑30 °C ~ +65 °CBaker Hugh… ‑ Storage Temperature:‑40 °C ~ +85 °C ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards
Mechanical Data
‑ Dimension(W×H×D):25.4 mm ×120.7 mm ×251.5 mm ‑ Weight: approx 0.40 kg
Core Functions
- Configurable alarm‑drive logic: Each relay channel supports AND / OR voting logic; trigger sources can select Alert, Danger, module fault Not‑OK status from any monitor channel inside rack.
- Relay mode configuration: Hardware toggle switch for Normally‑Energized / Normally‑De‑energized; software configurable latching or non‑latching output mode.
- External interlock driving: Output dry‑contact signal for field alarm indicator, turbine / gas‑turbine protection trip interlock circuit.
- Multi‑module expansion: Multiple 3500/32M modules can be installed within one rack to expand relay output quantity.
- Self‑diagnosis: Monitors internal working status, reports fault events to rack system log.
- Functional‑safety capability: Supports SIL‑2 safety‑related protection application with certified hardware set.
Installation, Replacement & Critical Warnings
- Module supports hot‑swap; monitor measurement & protection logic keep running during hot‑swap, relay output will be temporarily disconnected.
- Compatibility warning: ‑ Cannot directly replace old‑generation 125712‑01. Backplane definition and contact parameters differ. ‑ Must match rear I/O board 125720‑02, cannot use legacy 125720‑01. ‑ Verify rack firmware version before replacement; firmware mismatch may cause relay logic anomaly.
- For TMR triple‑redundant protection system, multi‑relay voting configuration shall be implemented to realize fault‑tolerant protection.
- After replacement, check OK and channel LED status; download rack configuration project, verify each relay action and voting‑logic function.
-
Common failure mode: Relay‑contact burnout under over‑current load; input‑circuit surge damage. Must operate within contact rating limits.





-300x300.jpg)


Reviews
There are no reviews yet.