Description
Hardware & Electrical Specifications
‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI rack, cooperates with 3500/22M TDI module, requires M‑series system firmware ‑ Functional Type: Old‑Generation 4‑Channel Mixed‑Input Proximitor & Seismic Monitor ‑ Channel quantity: 4 multi‑functional input channels ‑ Supported transducers: ‑ Proximity probe:3300XL eddy‑current series ‑ Seismic: velocity sensor, acceleration transducer ‑ Probe excitation power:‑24 VDC supplied by module ‑ Programmable sensitivity: Proximity:100 mV/mil (3.94 mV/μm), 200 mV/mil (7.87 mV/μm) Acceleration:100 mV/g Velocity:20 mV/(mm/s) pk ‑ Frequency response:0.5 Hz ~ 15 kHz (‑3 dB) ‑ Measurement accuracy:max ±1 % full‑scale ‑ Typical power consumption:7.7 W, powered by rack backplane bus ‑ Front‑panel: Four BNC buffered transducer output connectors; status LED: OK, TX/RX, per‑channel fault indicators ‑ Matching Parts: Main‑board 140734‑02 must pair with corresponding rear I/O board (multiple part‑number options for different sensor combinations, sold separately) ‑ Hot‑swap: Supports hot‑swap; during replacement, four channels of this module lose measurement & protection; other rack modules keep running normally. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2 capable within complete certified 3500 system set; ATEX / UL hazardous‑area approvals available.
Environmental Specifications
‑ Operating Temperature:‑30 °C ~ +65 °C ‑ Storage Temperature:‑40 °C ~ +85 °C ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards
Mechanical Data
‑ Dimension(W×H×D):25.4 mm ×120.7 mm ×251.5 mm ‑ Weight: approx 0.92 kg
Core Functions
- Mixed‑sensor signal conditioning: Supply‑24 VDC for proximity probes; condition seismic velocity / acceleration signals. One module processes both shaft‑relative and casing‑absolute vibration.
- Multi‑mode measurement: Channel‑pair configurable for radial vibration, thrust position, differential expansion, eccentricity REBAM, casing vibration, shaft‑absolute measurement.
- Phase‑related analysis: Accept rack‑wide Keyphasor timing reference, calculate 1X/2X amplitude & phase angle, support start‑up / coast‑down transient waveform capture.
- Two‑level alarm processing: Alert and Danger setpoints with configurable delay; generate rack system events, trigger relay‑module hardware alarm/trip output.
- Analog output: Each channel provides isolated 4‑20 mA output via rear I/O board for DCS data acquisition.
- Buffered BNC outputs: Front‑panel short‑circuit‑protected BNC copies raw transducer signal for portable field diagnostic instrument connection.
Installation, Replacement & Critical Warnings
- Supports hot‑swap; the four channels of this module lose measurement & protection during pulling‑out; other rack modules keep running.
- Compatibility warning: ‑ Cannot drop‑in replace 3500/40M‑140734‑01. Rear I/O boards are different; cross‑replacement must change rear I/O card and verify rack firmware version. ‑ Multiple rear I/O board variants for 140734‑02; select correct I/O part‑number according to on‑site sensor type (proximity / seismic mixed‑configuration). ‑ TMR triple‑redundant rack requires three identical 140734‑02 modules for three‑way redundant measurement.
- After replacement, check OK and channel LED status; download rack configuration project, verify gap/vibration reading, alarm threshold and 4‑20 mA output function.
-
Common failure mode:‑24 VDC transducer power circuit damage, BNC buffer‑circuit surge damage, component aging; transducer cable short‑circuit may burn front‑end conditioning circuit.





-300x300.jpg)


Reviews
There are no reviews yet.