Bently 3500-53 133388-01 Overspeed Detection Main Board

133388‑01 is safety‑critical electronic overspeed protection module for 3500 TSI rack, compliant with API‑670 / API‑612 overspeed protection requirements. It accepts pulse signals from proximity probes or magnetic pick‑up sensors, executes high‑speed overspeed detection and hardware trip output. This module is designed for machine safety trip, different from indication‑only 3500/50 tachometer module.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI rack, cooperates with 3500/22M TDI module, requires M‑series system firmware, redundant rack power supply required for safety application ‑ Functional Type: 2‑Channel Safety‑Grade Electronic Overspeed Detection Module ‑ Channel quantity: 2 independent pulse input channels ‑ Supported transducers: 3300XL proximity probes, magnetic pick‑up sensors ‑ Probe excitation power:‑24 VDC supplied by module ‑ Input signal range:+10 V ~ ‑24 V ‑ Input impedance:20 kΩ ‑ Measuring range: 1 ~ 99999 RPM ‑ Measurement accuracy:<100 RPM: ±0.1 RPM; 100‑10000 RPM: ±1 RPM; >10000 RPM: ±0.01 % reading ‑ Max input frequency:20 kHz ‑ Typical power consumption:8.0 W, powered by rack backplane bus ‑ Front‑panel Indicators: OK LED, TX/RX LED, Bypass LED, Test Mode LED, Alarm LED; one short‑circuit‑protected BNC buffered signal output ‑ Matching Parts: Main‑board 133388‑01 must pair with rear I/O board 133396‑01, sold separately ‑ Hot‑swap: Supports hot‑swap; during replacement, two‑channel overspeed protection of this module loses effectiveness; for safety practice, power‑off slot before plug‑pull on running protection rack. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2 capable within complete certified 3500 overspeed voting system set; ATEX / UL hazardous‑area approvals available.

Environmental Specifications

‑ Operating Temperature:‑30 °C ~ +65 °C ‑ Storage Temperature:‑40 °C ~ +85 °C ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards

Mechanical Data

‑ Dimension(W×H×D):241.3 mm ×24.4 mm ×241.8 mm ‑ Weight: approx 0.82 kg

Core Functions

  1. Pulse‑signal conditioning: Supply‑24 VDC for proximity probes; condition magnetic pick‑up pulse signals for overspeed acquisition.
  2. Safety‑grade overspeed detection: High‑response overspeed trip logic, supports multi‑module 2‑out‑of‑2 / 2‑out‑of‑3 voting architecture to improve safety and reduce false‑trip probability.
  3. Flexible parameter configuration: Events‑per‑turn, overspeed trip setpoint, alarm setpoint, trip hold‑off delay configurable. Stores peak speed value.
  4. Hardware trip & alarm output: Overspeed condition triggers hardware relay trip output; speed alarm generates rack system events.
  5. Analog output: Each channel provides isolated 4‑20 mA output via rear I/O board for DCS speed display and data acquisition.
  6. Buffered BNC output: Front‑panel BNC copies raw transducer signal for portable field diagnostic instrument connection.
  7. Self‑diagnosis: Continuous transducer cable fault detection, report module hardware fault to rack system log.

Installation, Replacement & Critical Warnings

  1. Hardware hot‑swap is electrically supported; for safety‑related overspeed rack, power‑off corresponding slot before insert / remove module to avoid protection loss risk.
  2. Compatibility warning: ‑ Cannot drop‑in replace 3500/50‑133388‑02 tachometer module; must use matched rear‑I/O board 133396‑01, verify rack firmware version. ‑ For safety overspeed application, adopt 2‑out‑of‑3 voting system with three identical 133388‑01 modules and rack redundant power supply, follow API‑670 requirement strictly. ‑ Magnetic pick‑up sensors have poor low‑speed performance; proximity probes are preferred for overspeed protection input.
  3. After replacement, check OK / Bypass / Test‑Mode LED status; download rack configuration project, complete overspeed simulation trip test, verify speed reading, trip threshold and 4‑20 mA output function.
  4. Common failure mode:‑24 VDC transducer power circuit damage, input‑circuit surge damage, component aging; transducer cable short‑circuit may burn front‑end conditioning circuit.