Bently 3500-60 163179-01 Temperature Monitor Main Board

163179‑01 is 6‑channel temperature monitor module for 3500 TSI machinery protection rack, compliant with API‑670 standard. It supports mixed‑mode input of RTD resistance temperature detectors and TC thermocouples on each channel, for bearing metal temperature, stator winding temperature, lube‑oil temperature and other process‑temperature monitoring. Configured via 3500 Rack Configuration Software.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI rack, cooperates with 3500/22M TDI module ‑ Functional Type: 6‑Channel RTD / TC Temperature Monitor Module ‑ Channel quantity: 6 multi‑functional temperature input channels ‑ Supported transducers:  ‑ RTD: Pt‑100(α=0.00385), Nickel, Copper RTD  ‑ Thermocouple: Type J, K, T, E ‑ RTD excitation current:925 ± 15 μA @25 ℃ ‑ Input impedance: ≥10 MΩ per leadBaker Hugh… ‑ Measuring range:‑200 ℃ ~ +1000 ℃ (depends on sensor type) ‑ Measurement accuracy: ±1~3 ℃ (varies by sensor and range) ‑ Typical power consumption:7 W, powered by rack backplane busBaker Hugh… ‑ Front‑panel Indicators: OK LED, TX/RX LED, Bypass LED ‑ Matching Parts: Main‑board 163179‑01 must pair with corresponding dedicated rear I/O board (non‑isolated / TC‑isolated options, sold separately) ‑ Hot‑swap: Supports hot‑swap; during replacement, six‑channel temperature measurement is temporarily invalid; other rack modules keep running normally. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2 capable within complete certified 3500 TMR system set; ATEX / UL hazardous‑area approvals available.

Environmental Specifications

‑ Operating Temperature:0 ℃ ~ +65 ℃ ‑ Storage Temperature:‑40 ℃ ~ +85 ℃ ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards

Mechanical Data

‑ Dimension(W×H×D):241.3 mm ×24.4 mm ×241.8 mm ‑ Weight: approx 0.91 kg

Core Functions

  1. Multi‑sensor signal conditioning: Process RTD and thermocouple signals, mixed‑sensor configuration allowed on different channels.
  2. Multi‑point temperature monitoring: Bearing metal temperature, lube‑oil temperature, motor stator temperature, casing and process temperature measurement.
  3. Flexible alarm configuration: Alert and Danger temperature setpoints with configurable delay; generate rack system events, trigger relay‑module alarm output.
  4. TMR redundant support: Can form triple‑modular‑redundant system with three identical modules for high‑safety machinery protection application.
  5. Self‑diagnosis: Continuous open‑circuit / short‑circuit fault detection for RTD and TC sensors; report module hardware fault to rack system log.

Installation, Replacement & Critical Warnings

  1. Supports hot‑swap; six‑channel temperature measurement loses effectiveness during pulling‑out; other rack modules keep running.
  2. Compatibility warning: ‑ Multiple rear I/O variants for 163179‑01; select non‑isolated or TC‑isolated I/O card according to site sensor type and anti‑interference requirement. ‑ Distinguish from 3500/61; 3500/61 adds recorder analog output function, main‑board and rear‑I/O are not interchangeable with 3500/60Baker Hugh…. ‑ For TMR triple‑redundant configuration, three identical 163179‑01 modules must be installed in adjacent slots of rack.
  3. After replacement, check OK / Bypass LED status; download rack configuration project, verify temperature reading and alarm trigger function.
  4. Common failure mode: Front‑end signal conditioning circuit damage, component aging; sensor cable short‑circuit / open‑circuit may affect channel measurement.

Reviews

There are no reviews yet.

Be the first to review “Bently 3500-60 163179-01 Temperature Monitor Main Board”

Your email address will not be published. Required fields are marked *