Description
Hardware & Electrical Specifications
‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI rack, cooperates with 3500/22M TDI module ‑ Functional Type: 6‑Channel Standard Analog Process‑Variable Monitor Module ‑ Channel quantity: 6 independent analog input channels ‑ Supported input signals: ‑ Current: 4‑20 mA ‑ Voltage: −10 Vdc ~ +10 Vdc ‑ Input impedance: ±10 V I/O:1 MΩ; 4‑20 mA I/O:50 Ω ‑ Isolation: Isolated I/O version supports 500 V channel‑to‑ground isolation ‑ Measurement accuracy: ±0.1 % full‑scale ‑ Typical power consumption:7.0 W, powered by rack backplane bus ‑ Front‑panel Indicators: OK LED, TX/RX LED, Bypass LED ‑ Matching Parts: Main‑board 163179‑03 must pair with corresponding dedicated rear I/O board (multiple variants sold separately) ‑ Hot‑swap: Supports hot‑swap; during replacement, six‑channel process‑variable measurement is temporarily invalid; other rack modules keep running normally. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2 capable within complete certified 3500 TMR system set; ATEX / CSA hazardous‑area approvals availableBaker Hugh….
Environmental Specifications
‑ Operating Temperature:0 ℃ ~ +65 ℃ ‑ Storage Temperature:‑40 ℃ ~ +85 ℃ ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards
Mechanical Data
‑ Dimension(W×H×D):241.3 mm ×24.4 mm ×241.8 mm ‑ Weight: approx 0.82 kg
Core Functions
- Standard analog‑signal conditioning: Process 4‑20 mA transmitter current signal and ±10 Vdc voltage signal.
- Multi‑type process‑variable monitoring: Pressure, flow, liquid‑level, compressor suction‑discharge pressure, active‑power and other process‑parameter acquisition.
- Flexible alarm configuration: Alert and Danger setpoints with configurable delay; generate rack‑system events, trigger relay‑module alarm output.
- TMR redundant support: Can form triple‑modular‑redundant system with three identical modules for high‑safety machinery‑protection application.
- Self‑diagnosis: Detect transmitter loop fault, open‑loop / short‑loop condition; report module hardware fault to rack‑system log.
Installation, Replacement & Critical Warnings
- Supports hot‑swap; six‑channel process‑variable measurement loses effectiveness during pulling‑out; other rack modules keep running.
- Compatibility warning: ‑ Multiple rear I/O variants for 163179‑03; select voltage‑type, isolated‑4‑20 mA or intrinsic‑safety‑barrier I/O according to site‑transmitter type and explosion‑proof requirement. ‑ Cannot swap main‑board or rear‑I/O between 3500/62 and 3500/60 / 3500/61 temperature‑monitor modules. ‑ For TMR triple‑redundant configuration, three identical 163179‑03 modules must be installed in adjacent slots of rack.
- After replacement, check OK / Bypass LED status; download rack‑configuration project, verify analog reading and alarm‑trigger function.
-
Common failure mode: Front‑end signal‑conditioning‑circuit damage, component aging; transmitter‑loop short‑circuit / open‑circuit may affect channel measurement.




-300x300.jpg)