Bently 3500-65 145988-02 16‑Channel Temperature Monitor Main Board

145988‑02 is high‑density 16‑channel temperature monitor module for 3500 TSI machinery‑protection rack, API‑670 compliantBaker Hugh…. It supports mixed‑input of RTD and isolated‑tip thermocouple sensors, for large‑quantity temperature‑point acquisition such as multi‑bearing metal temperature, lube‑oil temperature, motor/generator stator winding temperature, casing and auxiliary‑system temperature. Compared with 6‑channel 3500/60 & 3500/61, it greatly improves channel density, saving rack slots for multi‑temperature‑point projects.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 3500‑05 full‑size / mini TSI rack, cooperates with 3500/22M TDI module ‑ Functional Type: 16‑Channel High‑Density RTD / Isolated‑Tip‑TC Temperature Monitor Module ‑ Channel quantity: 16 multi‑functional temperature input channels ‑ Supported transducers:  ‑ RTD: Pt‑100(α=0.00385), Ni‑120, Cu‑10 (2‑wire /3‑wire /4‑wire)  ‑ Thermocouple: Isolated‑tip Type J, K, T, E, N, R, S ‑ RTD excitation current:925 μA typical ‑ Input impedance: ≥1 MΩ per leadBaker Hugh… ‑ Measuring range:‑200 ℃ ~ +1760 ℃ (depends on sensor type) ‑ Measurement accuracy: RTD ±0.1 %FS; TC ±1‑2 ℃; built‑in cold‑junction compensation for thermocouple ‑ Scan rate: All‑channels update within 1.6 seconds ‑ Typical power consumption:3 W, powered by rack backplane busBaker Hugh… ‑ Front‑panel Indicators: OK LED, TX/RX LED, Bypass LED ‑ Matching Parts: Main‑board 145988‑02 must pair with rear I/O:172103‑01(Internal Termination) or 172109‑01(External Termination), sold separatelyBaker Hugh… ‑ Hot‑swap: Supports hot‑swap; during replacement, sixteen‑channel temperature measurement is temporarily invalid; other rack modules keep running normally. ‑ PCB Coating: Conformal coated for G3 harsh industrial cabinet environment ‑ Safety Certification: SIL‑2 capable within complete certified 3500 TMR system set; ATEX, CE, CSA hazardous‑area approvals available

Environmental Specifications

‑ Operating Temperature:‑30 ℃ ~ +65 ℃ ‑ Storage Temperature:‑40 ℃ ~ +85 ℃ ‑ Relative Humidity:5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 power‑plant cabinet EMC standards

Mechanical Data

‑ Dimension(W×H×D):241.3 mm ×24.4 mm ×241.8 mm ‑ Weight: approx 0.91 kgbentlyplc

Core Functions

  1. Multi‑sensor signal conditioning: Process RTD and isolated‑tip thermocouple signals, mixed‑sensor configuration allowed on different channels.
  2. High‑density multi‑point temperature monitoring: Bearing‑metal temperature, lube‑oil temperature, generator‑stator temperature, casing and auxiliary‑system‑temperature measurement, saving rack slot resources.
  3. Flexible alarm configuration: Alert and Danger temperature setpoints with configurable delay and hysteresis; generate rack‑system events, trigger relay‑module alarm output.
  4. TMR redundant support: Can form triple‑modular‑redundant system with three identical modules installed in adjacent slots for high‑safety machinery‑protection applicationBaker Hugh….
  5. Self‑diagnosis: Continuous open‑circuit / short‑circuit fault detection for RTD and TC sensors; report module hardware fault to rack‑system log.

Installation, Replacement & Critical Warnings

  1. Supports hot‑swap; sixteen‑channel temperature measurement loses effectiveness during pulling‑out; other rack modules keep running.
  2. Compatibility warning: ‑ Two rear‑I/O options: internal‑termination (direct wiring to rear‑card) or external‑termination (match external terminal‑block 172115‑01). Select I/O type according to site‑wiring schemeBaker Hugh…. ‑ Cannot swap main‑board or rear‑I/O between 3500/65 and 3500/60 / 3500/61 temperature‑monitor modules. ‑ TMR triple‑redundant mode requires three identical 145988‑02 modules to be installed in adjacent slots of rack.
  3. After replacement, check OK / Bypass LED status; download rack‑configuration project, verify temperature reading and alarm‑trigger function.
  4. Common failure mode: Front‑end signal‑conditioning‑circuit damage, component aging; sensor‑cable short‑circuit / open‑circuit may affect channel measurement.