Description
Hardware & Electrical Specifications
‑ Model: DS200KLDCG1AAA ‑ Part Number: DS200KLDCG1AAA ‑ Module Type: Mark V Turbine Control Key‑LED‑Display HMI PCB Board (KLDC)Moore Auto… ‑ Mounting: Cabinet front‑panel four‑corner screw fixed panel‑mount ‑ Power supply: +5 VDC supplied from Mark V rack backplane; auxiliary power for display driving circuits ‑ Display resources: 21 pieces 4‑character 16‑segment alphanumeric LED display modules; 32 multi‑color status/alarm LED indicators ‑ Operator input: Integrated membrane keypad for local turbine‑operation commands ‑ Configuration components: 1 on‑board hardware jumper for display‑bus parameter setting; partial jumper positions reserved for factory test only, prohibited for on‑site adjustmentMoore Auto… ‑ Connectors: Single rear 40‑pin connection strip for Mark V system‑bus communicationMoore Auto… ‑ Communication: Parallel bus interface exchanging real‑time data, set‑point and fault‑alarm signals with Mark V CPU boards ‑ PCB treatment: Industrial conformal‑coated multilayer circuit board (‑AAA revision) ‑ Compatibility note: Exclusively for GE Speedtronic Mark V turbine‑control platforms; not drop‑in compatible with Mark VI / Mark VIe systems. After replacement, strictly duplicate original jumper‑configuration, guarantee 40‑pin connector full engagement, verify display output, LED status and keypad‑key response, cross‑check data consistency with controller diagnostic menus.
Environmental Specifications
‑ Operating temperature: 0 ℃ ~ +60 ℃ ‑ Storage temperature: −40 ℃ ~ +85 ℃ ‑ Relative humidity: 5%‑95% non‑condensing ‑ Installation location: Indoor turbine‑control cabinet, Pollution Degree 2, IP20 ‑ EMC compliance: Industrial EMC requirements for power‑generation turbine‑control‑room equipment ‑ Certifications: CE, UL compliant for power‑plant control‑system components
Mechanical Data
‑ Board dimension: 310 mm × 240 mm ‑ Mounting: Four‑point screw fixed front‑panel mounting ‑ Weight: approx 1.2 kg
Main Functions
- Real‑time local HMI for Mark V turbine‑control system: displays turbine speed, load, temperature, pressure, alarm‑fault codes and unit permissive‑status via 21 groups of alphanumeric LED displays and 32‑channel status‑LED array.
- Membrane keypad realizes local manual‑operation functions: parameter browsing, set‑point modification, alarm reset, operating‑mode switching and diagnostic‑menu navigation.
- Communicates with Mark V main CPU boards over rear 40‑pin system‑bus connector, completes bidirectional transmission of operating‑set‑point, real‑time process‑data and fault‑alarm‑information. Single configurable jumper adjusts display‑bus operating parameters; factory‑reserved test‑jumper positions shall not be altered on‑site.
- Visual indication supports daily on‑site monitoring, commissioning and fault‑diagnosis maintenance work.
Installation & Wiring Requirements
- Cut off rack control power before installation or replacement. Non‑hot‑swappable. ESD wrist‑strap protection is mandatory during board handlingMoore Auto….
- Secure DS200KLDCG1AAA onto cabinet front‑panel with four mounting screws. Reproduce jumper‑configuration exactly consistent with original‑board hardware settings. Confirm rear 40‑pin connection strip fully mated.
- System‑bus wiring must strictly follow Mark V system‑wiring drawings. Reliable protective‑earth connection for control cabinet is mandatory.
- After replacement: Restore rack control power. Verify each group of display modules and LED‑lamp status. Test every keypad key response, confirm local parameter‑write‑in function works normally. Cross‑check display read‑out against controller internal diagnostic‑menu values.
- Replacement note: Wrong‑jumper‑setting or poor 40‑pin‑connector contact will cause display‑data disorder, keypad‑input failure or loss of local‑operation function. Full‑system HMI‑function verification test is mandatory before turbine unit putting‑into‑service.