Description
Hardware & Electrical Specifications
‑ Manufacturer: GE General Electric ‑ Compatible System: Speedtronic Mark‑V Turbine Control ‑ Functional Acronym: TBQD (RST Extended Analog Termination Board) ‑ Signal Types Handled: • Auxiliary 4‑20 mA analog current loop inputs from field transmitters • LVDT/R position feedback signals • Extended analog milliamp output signals ‑ Terminal Blocks: 2 screw‑type high‑density terminal blocks for field wiring connection ‑ Inter‑Board Connectors: 3 ×34‑pin ribbon‑cable headers for connection to core controller boards ‑ On‑Board Jumpers: Configurable Berg‑style jumpers for signal routing and channel assignment. All jumper positions must be exactly duplicated during replacement ‑ Protection Circuitry: TVS diodes and clamping capacitors for surge and transient suppression on field signal lines ‑ Power Source: Receives bias power from controller boards through multi‑pin ribbon connectors; no independent external power supply ‑ PCB Finish: Conformal coated multilayer FR‑4 PCB ‑ Compatibility Restriction: Works only for Mark‑V systems; not compatible with Mark‑VI / Mark‑VIe control racks.
Environmental Specifications
‑ Operating Temperature: 0 °C ~ +60 °C ‑ Storage Temperature: −40 °C ~ +85 °C ‑ Relative Humidity: 5%‑95 % non‑condensing ‑ Installation Environment: Control cabinet interior, Pollution Degree 2 ‑ EMC: Designed for power‑plant cabinet EMI and switching‑transient conditions
Mechanical Data
‑ Physical Dimension: approx 286 mm × 76 mm ‑ Mounting: Four‑corner screw mounting holes for direct cabinet back‑plate installation ‑ Weight: approx 0.30 kg
Core Functions
- Extended field‑signal termination: Provides additional screw terminals to expand analog I/O capacity together with TBQC termination board for field transmitters and LVDT/R position sensors.
- Transient surge protection: On‑board suppression components absorb field‑wiring induced voltage spikes, protecting downstream controller electronics.
- Configurable signal routing: Hardware jumpers define channel routing and signal assignment to match field device layout.
- Signal interconnection: Multi‑pin ribbon‑cable headers transmit analog and position feedback signals between field wiring and core processing boards.
- Test access: On‑board test points support convenient signal measurement for commissioning and on‑site troubleshooting.
Installation, Replacement & Critical Warnings
- Complete system power‑down and lock‑out procedure required before servicing. Non‑hot‑swappable. ESD wrist‑strap protection is mandatory when handling the PCB assembly.
- Record all original jumper positions prior to removal. Replacement board must replicate jumper settings 100 %; incorrect jumper configuration results in missing channels or erroneous process readings.
- Torque all screw‑terminal connections properly; loose terminals cause unstable and noisy analog signals. Secure all ribbon‑cable connectors firmly.
- After power restoration, perform signal loop‑check: verify analog input values, analog‑output drive levels and LVDT position feedback readings at controller side.
-
Common failure mode: Field‑wiring surges may damage onboard suppression components while leaving downstream main boards undamaged. Inspect protection components during failure assessment.