Description
Hardware & Electrical Specifications
‑ Manufacturer: GE General Electric ‑ Compatible System: Speedtronic Mark‑V Turbine Control ‑ Functional Acronym: TCQC (Overflow Analog I/O Expander Board) ‑ Signal Types Handled: • Auxiliary analog input signals from field transmitters and position sensors • High‑current analog outputs for hydraulic servo‑valve control ‑ Connectors: 3 ×40‑pin, 3 ×34‑pin, 1 ×16‑pin ribbon‑cable headers for inter‑board connection to TCCA and TBQC hardware ‑ On‑Board Jumpers: Total 24 configurable Berg‑style jumpers for signal routing, channel assignment and output‑drive mode selection. All jumper positions must be exactly duplicated during replacement ‑ Circuitry: On‑board D/A conversion and amplifier circuits for servo‑valve high‑current driving ‑ Power Source: Receives bias power from core rack backplane through multi‑pin ribbon connectors; no independent external power supply ‑ PCB Finish: Conformal coated multilayer FR‑4 PCB ‑ Compatibility Restriction: Works only for Mark‑V systems; not mechanically or electrically compatible with Mark‑VI / Mark‑VIe control racks.
Environmental Specifications
‑ Operating Temperature: 0 °C ~ +60 °C ‑ Storage Temperature: −40 °C ~ +85 °C ‑ Relative Humidity: 5%‑95 % non‑condensing ‑ Installation Environment: Control cabinet interior, Pollution Degree 2 ‑ EMC: Designed for power‑plant cabinet EMI and switching‑transient conditions
Mechanical Data
‑ Physical Dimension: approx 260 mm × 165 mm ‑ Mounting: Standard slot installation within Mark‑V R/S/T triple‑redundant core rack ‑ Weight: approx 0.81 kg
Core Functions
- Analog channel expansion: Supplements TCCA main analog board to process extra analog input signals for turbine process and position measurement.
- Servo‑valve high‑current drive: Converts digital control commands into amplified analog current signals to operate hydraulic servo‑valves for fuel, governor and steam valve regulation.
- Configurable signal routing: 24 hardware jumpers define channel allocation and output drive parameters to match site actuator configuration.
- Inter‑board signal transmission: Multi‑pin ribbon‑cable headers exchange analog signals between TCQC, TCCA controller board and TBQC field termination boards.
- Test access: On‑board test points support convenient signal measurement during commissioning and field troubleshooting.
Installation, Replacement & Critical Warnings
- Complete system power‑down and lock‑out procedure required before servicing. Non‑hot‑swappable. ESD wrist‑strap protection is mandatory when handling the PCB assembly.
- Record all original jumper positions before removing the original board. Improper jumper settings result in servo‑valve mis‑operation, missing analog channels or wrong process readings.
- Fasten all ribbon‑cable connectors securely; poor contact leads to intermittent control output and unstable valve action.
- After power restoration, perform full loop‑check: verify analog input readings, measure servo‑valve drive current outputs and confirm overall signal performance.
-
Common failure mode: Field‑wiring surge can damage output amplifier circuits on TCQC. Inspect corresponding TBQC termination boards when abnormal control behaviour occurs.