Basic Hardware Information
- Input channels: 8 independent strain‑gauge input channels
- Signal input range: Software configurable per‑channel: ±25 mV, ±50 mV, ±100 mV
- ADC resolution: 16‑bit sigma‑delta conversion; resolution reaches 0.8 µV / 1.6 µV / 3.2 µV corresponding to different ranges
- Conversion speed: 35 channels per second total sampling rate
- Input impedance: >1000 MΩ; maximum safe input voltage ±35 V DC/AC transient protection
- Excitation function: On‑board excitation voltage supply, supports excitation voltage monitoring and automatic compensation for excitation drift
- Backplane power consumption: Inrush 160 mA @5 VDC; steady‑state 30 mA @5 VDC
- Mechanical structure: Single‑slot rack‑mount module; non‑hot‑swappable
- Status indicators: Front‑panel LED indicators for module health and channel diagnostic status
- Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature ‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing
- Software configuration: Parameter setup completed via LogicMaster 90 software; individual unused channels can be disabled to reduce module response latency.
Core Functions & Features
- Direct interface for bridge‑type load‑cells and strain‑gauges, eliminates requirement for external signal transmitter hardware.
- Per‑channel independent range configuration; unused channels can be turned off to optimize sampling speed.
- Excitation voltage monitoring and compensation function reduces measurement deviation caused by excitation source fluctuation.
- Built‑in diagnostic functions: wire‑break detection, over‑range and under‑range alarm for each channel; fault status is mapped to PLC discrete input memory area.
- Supports software zero‑point offset and span calibration for field sensor correction; measured millivolt values are transferred to Series 90‑30 CPU via backplane bus.
On‑site Installation & Commissioning Notes
- Power off the entire PLC rack before inserting or removing HE693STG884; this module is non‑hot‑swappable. Take ESD protection measures during handling.
- Use shielded twisted‑pair cables for strain‑gauge field wiring. Separate sensor cables from high‑power cables to suppress electromagnetic noise. Keep cable length consistent for multi‑channel load‑cell groups.
- Complete hardware configuration in LogicMaster 90 software: define input range, enable‑disable channels, set digital filter parameters and alarm thresholds.
- Perform zero‑point calibration under no‑load condition, then execute span calibration using standard reference weight or force.
- After commissioning, apply known test load to verify reading accuracy and diagnostic response.
- Replacement note: General analog input modules cannot serve as direct substitutes; replacement must use identical part number.