IC200ALG327F is 12‑channel single‑ended voltage analog output module for GE Fanuc VersaMax PLC system. It receives digital output data from VersaMax CPU / network interface unit and converts to analog voltage signals to drive valves, actuators, variable‑speed drives and process field instruments. Jumper configurable for output range and fail‑safe state when communication lost. Requires external field power for output circuits. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IC200ALG327F ‑ Part Number:IC200ALG327F ‑ Module Type:VersaMax Voltage Analog Output Module ‑ Mounting:Installed on VersaMax carrier base IC200CHSxxx, DIN‑rail mounting ‑ Backplane power:5 VDC from carrier backplane, max 50 mA ‑ Field external power:18‑30 VDC for output circuit ‑ Output channels:12 single‑ended voltage output channels, one group isolation ‑ Output range:jumper selectable, bipolar −10 VDC ~ +10 VDC / unipolar 0‑10 VDC ‑ Resolution:13‑bit ‑ Max update time:15 ms for full 12‑channel update ‑ Communication interfaces:VersaMax backplane bus to CPU / NIUs ‑ Carrier base:Requires IC200CHS series carrier base unit ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:User‑side to logic isolation 250 VAC continuous, 1500 VAC 1‑min withstand; field‑power loss detection, hardware jumper for fail‑safe mode (hold last value or zero output on communication break) ‑ Compatibility note:Cannot run standalone; must match VersaMax carrier base and CPU firmware; full analog‑loop simulation test mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.28 kg ‑ Dimension:Standard single‑slot VersaMax module form‑factor ‑ Handling note:ESD‑sensitive analog circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Receive digital set‑point data from VersaMax CPU over backplane bus.
  2. Perform D/A conversion and output configurable analog voltage signals for field control devices.
  3. Jumper‑selectable fail‑safe behavior: hold last output value or force zero output upon communication loss or backplane power failure (external field power must remain alive).
  4. Detect loss of external field‑side power and report diagnostic fault status to PLC CPU.
  5. LED status indication:   ‑ Green OK LED:Backplane power present   ‑ Green FLD PWR LED:External field‑side power present

Installation & Wiring Requirements

  1. Cut off both backplane rack power and external field power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
  2. Insert module into VersaMax carrier base slot and lock firmly; set on‑board jumpers for output range and fail‑safe mode according to project requirement.
  3. Analog output wiring strictly follow GE VersaMax hardware manual; use shielded twisted‑pair cable, separate analog signal cables from high‑power cables, connect shielding to dedicated protective ground terminal.
  4. Complete protective grounding according to GE system specification.
  5. After replacement: power‑on step‑by‑step, verify OK and FLD‑PWR LED status, perform full‑channel output calibration test and communication‑loss fail‑safe simulation test.
  6. Replacement note: Verify hardware and firmware compatibility; full analog‑loop simulation test mandatory before unit put‑into‑service.