Description
Hardware & Electrical Specifications
‑ Model:IC200PWR001G ‑ Part Number:IC200PWR001G ‑ Module Type:VersaMax Backplane Power Supply Module ‑ Mounting:Snap‑on to CPU / NIU / IC200PWB001 booster carrier, DIN‑rail mounting ‑ Input power:18‑30 VDC, nominal 24 VDC, max input power 11 W ‑ Hold‑up time:10 ms minimum at nominal 24 VDC input ‑ Inrush current:20 A@24 VDC (6 ms max), 25 A@30 VDC (6 ms max) ‑ Output: • +5 VDC and +3.3 VDC backplane power • Total output current:max 1.5 A • 3.3 VDC max 0.25 A; 5 VDC current = total current minus 3.3 VDC consumption ‑ Terminals:Screw terminal block for DC‑24V input ‑ Compatible carrier:CPU base, NIU base, IC200PWB001 power booster carrier ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Reverse‑polarity protection, overload current‑limiting, short‑circuit shutdown, thermal protection; DC‑ internally connected to protective frame ground ‑ Compatibility note:Cannot run standalone; must match VersaMax carrier base; calculate total backplane current consumption before commissioning; full power‑loop test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.12 kg ‑ Dimension:Standard VersaMax power‑supply module form‑factor (39 × 133 × 49 mm) ‑ Handling note:ESD‑sensitive power circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Accepts external 24 VDC field power input, converts and supplies stable 5 VDC / 3.3 VDC power to VersaMax backplane for CPU, network interface and I/O modules.
- Works as main station power supply when attached to CPU/NIU carrier; acts as auxiliary booster power on IC200PWB001 for racks with high‑current I/O load.
- Built‑in hardware protection: reverse‑connection, short‑circuit, overload and over‑temperature protection to prevent damage to downstream backplane devices.
- LED status indication: ‑ Green OK LED:Input power normal and output healthy
Installation & Wiring Requirements
- Cut off external 24 VDC input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Snap module onto CPU / NIU / booster carrier, rotate locking latch to lock position for reliable mechanical and electrical contact.
- 24 VDC input wiring strictly follow GE VersaMax hardware manual GFK‑1504K; DC‑ must connect to cabinet protective ground; external MOV surge suppression is recommended at power input terminal; separate power cables from low‑signal analog cables.
- Complete protective grounding according to GE system specification.
- After replacement:power‑on step‑by‑step, verify OK LED status, measure backplane rail voltage, check all downstream I/O module power‑on status.
- Replacement note: Calculate total backplane current consumption to avoid overload; full power‑supply‑loop simulation test mandatory before unit put‑into‑service.


-1-1-300x300.jpg)


Reviews
There are no reviews yet.