Description
Hardware & Electrical Specifications
‑ Model:IC610MDL116A ‑ Part Number:IC610MDL116A ‑ Module Type:Series‑One 4‑Channel Differential Analog Input Module ‑ Mounting:Plug‑in into Series‑One I/O rack backplane slot ‑ Backplane power:5 VDC from rack backplane, typical consumption 180 mA ‑ Input channels:4 differential analog input channels ‑ Input signal types:jumper configurable 1‑5 VDC or 4‑20 mA field signals ‑ Input impedance:9.5 kΩ for voltage mode ‑ A‑D conversion:successive‑approximation ADC, 8‑bit resolution, max conversion time 2 ms per channel ‑ Accuracy:±1 % full‑scale at 25 ℃, max linearity error ±0.8 % FS ‑ Communication interfaces:Series‑One proprietary backplane bus to CPU ‑ Mechanical feature:module mechanical keying for anti‑mis‑insertion ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:transient surge suppression, differential common‑mode noise rejection, hardware self‑diagnosis ‑ Compatibility note:Cannot run standalone; must match Series‑One CPU and I/O rack; full analog‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.30 kg ‑ Dimension:Standard Series‑One single‑slot plug‑in module form‑factor ‑ Handling note:ESD‑sensitive analog acquisition circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Acquire differential‑mode analog signals from field 4‑20 mA / 1‑5 VDC transmitters and process sensors.
- Perform signal conditioning and A‑D conversion, transfer digital process values to Series‑One PLC CPU over backplane bus.
- Differential‑input architecture suppresses ground‑loop interference and industrial field common‑mode noise.
- LED status indication: ‑ Green LED:Module power and self‑test OK status
Installation & Wiring Requirements
- Cut off rack backplane power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert module fully into Series‑One rack slot and lock; set on‑board jumpers for each channel’s voltage/current mode according to field‑transmitter type.
- Analog‑signal wiring strictly follow GE Series‑One hardware manual; use shielded twisted‑pair cable, separate analog wiring from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on, verify OK LED status, perform channel calibration and signal‑loop fault simulation test.
- Replacement note: Verify CPU firmware compatibility; full analog‑loop simulation test mandatory before unit put‑into‑service.