Description
Hardware & Electrical Specifications
‑ Model:IC660ELB921M ‑ Part Number:IC660ELB921M ‑ Module Type:Genius‑bus PCIM ISA Carrier Board (Single‑Slot) ‑ Mounting:ISA‑slot installation inside industrial AT‑style PC chassis ‑ ISA bus power:5 VDC @ max 400 mA from host ISA backplane ‑ Supported daughter‑board:Single µGENI daughter‑board IC660ELB912 / IC660ELB912J ‑ Host memory requirement:Occupies 4‑byte memory address space on host ISA bus ‑ Genius‑bus baud‑rate:38.4k /76.8k /153.6k standard /153.6k extended baud‑rate (jumper setting) ‑ Genius‑bus connector:Screw terminal block on front‑bracket for shielded Genius‑bus cable ‑ Max slave capacity:Up to 30 Genius remote I/O blocks when matched with µGENI daughter‑board ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Genius‑bus transient surge suppression, ISA‑bus signal driving circuit, hardware jumper for baud‑rate and memory address configuration ‑ Compatibility note:Cannot run standalone; must install matching IC660ELB912(J) µGENI daughter‑board; ISA memory address & baud‑rate jumpers must match system configuration; full Genius‑bus simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Inside industrial control PC cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.48 kg ‑ Dimension:Standard single‑slot ISA full‑length AT‑form‑factor board ‑ Handling note:ESD‑sensitive circuit; contains ISA high‑speed logic circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- ISA‑bus carrier hardware for µGENI daughter‑board IC660ELB912(J), provides mechanical mounting and power supply for daughter‑board.
- Realizes electrical signal conversion between host ISA bus and Genius field‑bus physical layer, provides Genius‑bus field‑wiring terminal interface.
- On‑board jumpers configure ISA memory base address and Genius‑bus baud‑rate, consistent with Genius‑bus slave devices.
- LED status indication: ‑ Green GENI‑OK:µGENI daughter‑board power‑on and self‑test pass ‑ Green COMMS‑OK:Genius‑bus communication activity normal
Installation & Wiring Requirements
- Completely cut off industrial‑PC main power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling board.
- Insert IC660ELB921M into PC ISA slot and fasten bracket screw; install IC660ELB912(J) daughter‑board onto PCIM; set memory‑address and baud‑rate jumpers according to project configuration.
- Genius‑bus wiring strictly follow GE Genius hardware manual; use shielded twisted‑pair Genius‑bus cable; install terminating resistor at two physical ends of bus trunk; separate bus signal cables from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on industrial PC, verify GENI‑OK & COMMS‑OK LED status, load Genius driver software, perform bus‑scan and full I/O‑loop commissioning test.
- Replacement note: Verify ISA address no conflict with other PC peripheral cards; daughter‑board hardware revision compatibility check; full Genius‑bus‑loop simulation test mandatory before unit put‑into‑service.



-300x300.jpg)