Description
Hardware & Electrical Specifications
‑ Model:IC660TBA026M ‑ Part Number:IC660TBA026M ‑ Module Type:Genius Analog I/O Terminal Base Assembly ‑ Mounting:Panel or 35 mm DIN‑rail mounting ‑ Local block power terminals:115 VAC 47‑63 Hz /105‑145 VDC power input for whole block ‑ Field signal terminals:Screw‑clamp terminals for 6‑channel 4‑20 mA current‑source analog loops; wire gauge 0.5‑2.5 mm² (14‑24AWG) ‑ Communication interfaces:Dual Genius‑bus terminal blocks for primary / daisy‑chain bus wiring ‑ Mating electronics assembly:IC660EBA026 ‑ Mechanical:Latch locking mechanism for electronics unit installation; built‑in Genius‑bus address rotary switch on terminal base ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Field‑loop transient surge suppression; physical channel isolation barrier; no active logic circuit, purely passive termination hardware ‑ Compatibility note:Cannot work standalone; must pair with IC660EBA026 electronics assembly; full analog‑loop continuity test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +100 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 protection degree ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.90 kg ‑ Dimension:224 × 90 × 100 mm ‑ Handling note:ESD‑sensitive mating connector; anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Provide field‑wiring termination interface for 6‑channel 4‑20 mA analog transmitters and control instruments.
- Carry local block power input and Genius‑bus daisy‑chain bus terminals; host rotary address switch for Genius‑bus slave station address setting.
- Separable mechanical structure: electronics unit can be pulled out for maintenance without removing field instrument cables.
- Transfer analog field signals and Genius‑bus signals to mated IC660EBA026 electronics assembly via edge connector.
Installation & Wiring Requirements
- Cut off block local 115VAC/125VDC power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling terminal base.
- Mount IC660TBA026M firmly on panel or DIN‑rail; insert and lock IC660EBA026 electronics assembly; set Genius‑bus rotary address switch consistent with master configuration.
- Analog‑loop and Genius‑bus wiring strictly follow GE Genius hardware manual; use shielded twisted‑pair cable for analog and Genius‑bus; install bus terminator resistor at both physical ends of Genius trunk; separate signal cables from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on whole block, verify block self‑test status, perform full‑channel analog‑signal continuity test.
- Replacement note: Verify mechanical compatibility with electronics assembly; full analog‑loop simulation test mandatory before unit put‑into‑service.

-1-300x300.jpg)



Reviews
There are no reviews yet.