Description
Hardware & Electrical Specifications
‑ Model:IC670ALG230 ‑ Part Number:IC670ALG230 ‑ Module Type:Field‑Control 8‑Channel Current‑Source Analog Input Module ‑ Mounting:Plug‑in onto Field‑Control BIU base unit, DIN‑rail mounting ‑ BIU backplane power:Max 51 mA drawn from BIU backplane ‑ Field loop power:18‑30 VDC nominal 24 VDC; total module consumption max 210 mA including field loop current ‑ Input channels:8 single‑ended analog input channels, common ground group ‑ Signal range:Software configurable per‑channel: 0‑20 mA (default), 4‑20 mA; absolute max input 30 mA ‑ Resolution:12‑bit digital resolution; analog resolution 5.0 μAQualitrol ‑ Conversion time:Typical 60 μs per channel @1 MHz clockQualitrol ‑ Input impedance:Approx 250 Ω ‑ Filter:On‑board 1st‑order RC filter, typical cutoff frequency 160 Hz ‑ Diagnosis:Open‑wire detection (trigger below 2 mA for 4‑20 mA range); over‑range fault indication above 20 mA ‑ Communication interfaces:Field‑Control backplane to BIU, further to Genius‑bus ‑ Terminal:Removable screw‑clamp terminal block ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:1500 VAC 1‑minute withstand field‑to‑logic isolation; 250 VAC continuous isolation; transient surge suppression; hardware self‑diagnosis ‑ Compatibility note:Cannot run standalone; must match Field‑Control BIU unit; full analog‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.26 kg ‑ Dimension:Standard Field‑Control module form‑factor ‑ Handling note:ESD‑sensitive precision analog circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Collect 4‑20 mA /0‑20 mA current signals from field pressure, flow, level and temperature transmitters.
- Perform analog‑to‑digital conversion, transmit digital process values to BIU over local backplane, then upload to Genius‑bus master controller.
- Built‑in channel‑level fault diagnosis: open‑loop, over‑range detection, convenient for field‑side troubleshooting.
- LED status indication: ‑ Green OK:Module power‑on and self‑test pass
Installation & Wiring Requirements
- Cut off BIU rack power and field 24VDC loop power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC670ALG230 fully into Field‑Control BIU base slot and lock firmly.
- Analog‑loop wiring strictly follow GE Field‑Control hardware manual GFK‑0893G; use shielded twisted‑pair instrument cable; separate analog signal cables from high‑power cables, connect shielding to dedicated protective ground terminalQualitrol.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on, verify OK LED status, download module channel configuration, perform full‑channel signal test and fault‑simulation test.
- Replacement note: Verify BIU hardware and firmware compatibility; full analog‑loop simulation test mandatory before unit put‑into‑service.






Reviews