Description
Basic Hardware Information
‑ Supported bus protocol: GE Genius serial field‑bus ‑ Communication baud‑rate: 38.4 k, 53.6 k, 76.8 k, 153.6 kbaud (extended speed) selectable ‑ Genius drop‑address: rotary hardware switch, address range 0‑31, unique address required on same bus network ‑ I/O capacity: maximum 8 Field‑Control I/O modules on local station backplane ‑ Bus data capacity: 128‑byte input / 128‑byte output per bus scan cycle ‑ Power input: 90‑135 VAC or 105‑150 VDC; 47‑63 Hz; max 48 VA power consumption at AC input ‑ Backplane output: generates internal backplane power for local Field‑Control I/O modules ‑ Bus interface: dual screw‑terminal blocks for primary / redundant Genius bus; D‑Sub 9‑pin monitor port for handheld programmer connection ‑ Termination resistor options: supports 75 Ω / 100 Ω / 120 Ω / 150 Ω matched with Genius trunk cable type ‑ Isolation: galvanic isolation between Genius bus side and local I/O backplane circuits ‑ Status indicators: multi‑LED set: PWR, OK, RUN, BUS‑ACTIVE, FAULT diagnostic status lamps ‑ Mechanical: DIN‑rail or cabinet‑panel mounting; IP20 enclosure; weight approx 0.85 kg; non‑hot‑swappable for whole BIU unit under power‑on condition ‑ Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature ‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing ‑ Handling note: ESD‑sensitive hardware; anti‑static wrist‑strap required during maintenance work ‑ Compatibility: works with Series 90‑30 / Series 90‑70 Genius‑bus master controllers; compatible with IC660HHM501 handheld monitor‑programmer.
Core Functions & Features
- Acts as Genius‑bus slave NIU for Field‑Control station. Collects signal data from local discrete / analog I/O modules, transmits to Genius master PLC; receives output commands from master and drives local output modules.
- Dual bus terminals support daisy‑chain topology and optional media‑redundant Genius‑bus wiring for higher system reliability.
- Hardware rotary switch defines Genius drop‑station address; duplicate address will trigger bus conflict and whole‑network communication anomaly.
- Local station configuration parameters are stored inside BIU non‑volatile memory; configuration survives power‑off cycles. Hand‑held programmer can read fault statistics and modify station parameters on‑site without PLC software.
- Comprehensive diagnostic functions: bus error counter, local‑backplane module fault detection, loss‑of‑master monitoring, I/O‑module failure reporting; fault status can be read by master controller for alarm processing.
- Controls internal backplane power sequencing for local Field‑Control I/O modules, completes module initialization and data mapping during power‑up sequence.
On‑site Installation & Commissioning Notes
- Cut off BIU main power supply before installing or replacing IC670GBI102; do not perform hot‑swap for complete BIU unit under power‑on. Apply anti‑static protection during maintenance work.
- Mount unit on grounded DIN‑rail or cabinet panel; avoid locations with excessive vibration, high temperature and heavy oil‑mist accumulation.
- Use shielded twisted‑pair Genius‑bus trunk cable. Install matched termination resistor at the two physical ends of bus trunk line. Separate Genius‑bus signal cables from high‑voltage power wiring to suppress electromagnetic interference.
- Set rotary Genius drop‑address to an unused unique address on Genius network. Select baud‑rate matching master‑controller bus‑configuration and cable length.
- Complete station hardware configuration: define local‑backplane slot layout and installed I/O‑module types via PLC programming software or handheld programmer, download configuration to BIU. Corresponding drop‑station definition must also be configured inside Genius master‑controller project.
- After commissioning, verify BUS‑ACTIVE and RUN LED status; perform point‑to‑point I/O test between master PLC and Field‑Control station; validate analog‑channel accuracy and diagnostic response.
- Replacement note: After unit replacement, double‑check rotary drop‑address setting, confirm baud‑rate setting, re‑download station configuration and perform full‑system I/O point validation.
Common On‑site Abnormal Conditions
‑ BUS‑ACTIVE LED remains off: Wrong baud‑rate setting, missing bus termination resistor, damaged bus trunk cable, duplicate Genius drop‑address, master controller not configured for this drop address. ‑ FAULT LED illuminated: Local‑backplane defective I/O module, poor module‑seating on backplane socket, corrupted BIU station‑configuration data. ‑ Entire station no communication: Loss of BIU main AC/DC input power, internal BIU hardware failure. ‑ Intermittent station offline: Vibration‑induced bus‑terminal loose contact, inadequate shielding‑grounding, bus baud‑rate mismatch with actual cable length. ‑ Partial I/O modules unrecognized: Modules not fully latched on backplane socket, insufficient BIU backplane drive‑capacity, incompatible module‑firmware revision. ‑ Configuration lost after power‑cycle: BIU internal non‑volatile memory hardware anomaly; requires full station‑configuration re‑download.