Description
Hardware & Electrical Specifications
‑ Model:IC670MDL640 ‑ Part Number:IC670MDL640 ‑ Module Type:Field‑Control 16‑Point 24VDC Pos/Neg Logic Discrete Input Module ‑ Mounting:Plug‑in onto Field‑Control BIU base unit, DIN‑rail mounting ‑ BIU backplane consumption:75 mA typical (all points ON); max 83 mA ‑ Input channels:16‑point discrete inputs, single common group ‑ Input voltage range:0‑30 VDC, nominal 24 VDC ‑ Logic threshold: • Positive‑logic ON: +15 V ~ +30 V; OFF: 0 ~ +5 V • Negative‑logic ON: ‑15 V ~ ‑30 V; OFF: 0 ~ ‑5 V ‑ Input current:3‑8 mA per channel ON‑state; 0‑1.5 mA OFF‑state; typical 7.5 mA@24VDC ‑ Input impedance:3 kΩ typical ‑ Response time:ON / OFF typical 6 ms; maximum 10 ms ‑ Isolation:250 VAC continuous; 1500 VAC 1‑minute withstand (field‑to‑logic bus); no isolation between channels within group ‑ Communication interfaces:Field‑Control local backplane to BIU, further to Genius‑bus ‑ Terminal:Removable screw‑clamp terminal block ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Field‑side transient surge suppression, hardware self‑diagnosis; no individual channel fuse ‑ Compatibility note:Cannot run standalone; must match Field‑Control BIU unit; full discrete‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.23 kg ‑ Dimension:Standard Field‑Control module form‑factor ‑ Handling note:ESD‑sensitive digital circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Collect digital status signals from field limit switches, proximity sensors, push‑buttons and relay auxiliary contacts, supports both positive‑logic and negative‑logic wiring modes.
- Convert field discrete signals into digital data, transmit to BIU over local backplane and upload to Genius‑bus master PLC.
- LED status indication: ‑ Green PWR:Module backplane power‑on and self‑test pass ‑ 16 individual channel LEDs:Real‑time status for each discrete input point
Installation & Wiring Requirements
- Cut off BIU rack power and field‑side 24VDC signal power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC670MDL640 fully into Field‑Control BIU base slot and lock firmly.
- Field‑signal and Genius‑bus wiring strictly follow GE Field‑Control hardware manual GFK‑0890G; use shielded twisted‑pair cable; separate signal cables from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on, verify PWR & channel LED status, perform full‑channel signal trigger test.
- Replacement note: Verify BIU hardware and firmware compatibility; full discrete‑loop simulation test mandatory before unit put‑into‑service.


-300x300.jpg)



Reviews