GE IC690RFH008 Genius Remote Fiber Optic Repeater Module

IC690RFH008 is a Genius‑bus fiber‑optic repeater module for GE Fanuc Genius distributed I/O system. It converts Genius electrical bus signal into optical signal, extends Genius‑bus communication distance, realizes electrical‑isolation between different bus segments. It features two ST‑type fiber ports for multi‑mode fiber connection, and two Genius electrical bus terminal ports for copper‑wired bus segments. It works as transparent repeater, no software configuration required, does not occupy Genius bus address. Effectively eliminates ground‑loop interference and long‑distance industrial field noise. Widely used in Series‑90‑70, Field‑Control Genius systems. Product status: Obsolete, spare‑part only supply available。

Email:2306444920@qq.com
Phone:+86 17759635229

Description

Hardware & Electrical Specifications

‑ Model:IC690RFH008 ‑ Part Number:IC690RFH008 ‑ Module Type:Genius Fiber‑Optic Repeater ‑ Mounting:Panel or 35 mm DIN‑rail mounting, standalone unit ‑ Power supply:18‑30 VDC nominal 24 VDC; typical power consumption 120 mA ‑ Fiber interface:Dual ST‑connector for multi‑mode optical fiber; recommended fiber 62.5/125 µm multi‑mode ‑ Maximum fiber distance:2000 meters under 153.6k baud‑rate; longer distance at lower baud‑rate ‑ Electrical Genius‑bus ports:Two screw‑terminal ports for copper Genius‑bus daisy‑chain wiring ‑ Supported baud‑rate:38.4k /76.8k /153.6k standard /153.6k extended baud‑rate, auto‑detect ‑ Operation mode:Transparent repeater, no Genius‑bus node address ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Surge suppression on Genius copper bus side; complete galvanic isolation between different bus segments via optical link ‑ Compatibility note:Cannot run standalone; must match Genius‑bus baud‑rate of whole system; install bus terminators at physical ends of each copper bus segment; full Genius‑bus communication test mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.75 kg ‑ Dimension:140 × 85 × 110 mm ‑ Handling note:ESD‑sensitive circuit; avoid direct eye exposure to optical fiber transmit port; anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Genius‑bus signal media converter, converts electrical Genius‑bus signal to optical signal, extends communication transmission distance for Genius distributed I/O network.
  2. Provides complete electrical isolation between copper bus segments, suppresses ground‑loop noise and heavy‑industrial electromagnetic interference.
  3. Transparent repeater device, no PLC software configuration, does not consume Genius bus address resource.
  4. LED status indication:   ‑ Green POWER:Module 24VDC power‑on indicator   ‑ Green LINK‑A / LINK‑B:Fiber‑link status for each optical channel   ‑ BUS‑ACT:Genius‑bus communication activity indicator

Installation & Wiring Requirements

  1. Cut off module 24VDC power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling unit.
  2. Mount IC690RFH008 firmly on panel or DIN‑rail; connect multi‑mode ST fiber cables; connect copper Genius‑bus wiring to electrical terminal ports.
  3. System wiring strictly follow GE Genius hardware manual; install bus terminator resistor at both physical ends of every copper bus segment; keep fiber path away from high‑voltage / high‑power cables.
  4. Complete protective grounding according to GE system specification.
  5. After replacement: power‑on module, verify POWER, LINK‑A/B LED status, perform Genius‑bus scan and full I/O‑loop commissioning test.
  6. Replacement note: Confirm fiber core cleanliness and ST connector installation; match system Genius baud‑rate; full Genius‑bus‑loop simulation test mandatory before unit put‑into‑service.